Accessories:
 Connection cable with moulded M12x1 coupling
socket.
 M12x1 coupling socket for self-assembly.

1.2 Intended use

The magnetic inductive flow sensor VMI must only be used for measuring and metering liq-
uids with a minimum conductivity of 50 μS/cm.
WARNING! No safety component!
The magnetic inductive flow sensors of the VMI series are no safety components in ac-
cordance with Directive 2006/42/EC (Machine Directive).
 Never use the VMI as a safety component.
The operational safety of the device supplied is only guaranteed by intended use. The speci-
fied limits ( § 9 "Technical data") may under no circumstances be exceeded.
Before installation, check whether the wetted materials of the device are suitable for the liq-
uid used ( § 9.2 "Materials table").
Measuring tube empty (or partially filled). / Conductivity too low.
The green LED may blink irregularly if the measuring tube of the VMI is empty or partial-
ly filled or if the conductivity of the fluid being used is too low. Random pulses will be
present at the output, but they do not represent an actual flow.
 Ensure that the measuring tube of the VMI is always completely filled
( § 4.1 "Installation instructions").
 Ensure that the conductivity of the fluid is at least 50 μS/cm.

1.3 Exclusion of liability

We accept no liability for any damage or malfunctions resulting from incorrect installation,
in-appropriate use of the device or failure to follow the instructions in this operating manual.
Technical changes reserved