46
CARACTéRISTIQuES TEChNIQuES
TEChNICAl ChARACTERISTICS - TEChNISChE DATEN - CARATTERISTIChE TECNIChE -
TEChNISChE kENMERkEN - CARACTERÍSTICAS TéCNICAS - CARACTERÍSTICAS TéCNICAS
GB
COMPLIANCE
SYSTEM CONNECTION
Supply types / number of wires
Management
frequency
SUPPLY
CONSUMPTION
Supply
current circuit
CURRENT (TRMS)
Starting current (ist)
Minimum current (imin)
transition current (itr)
reference current (iref)
Permanent overload (imax)
Short-term over-current
VOLTAGE (TRMS)
Direct measurement
Permanent overload
POWERS
active
reactive
resolution
ENERGY
active
reactive
total and partial metering
Bidirectional metering (ea+ and ea-)
resolution
ACCURACY
active energy
TARIFFS
tariff management
number of tariffs managed
tariff exchange input
METROLOGICAL LED
impulse weight
colour
DISPLAY
type
refresh time
Back-lighting illumination time
list of functions displayed
* functions available only via communication, the complete list of these functions is given in the down-
loadable JBUS/MoDUS communication table.
COUNTIS E43 - Ref.: 537 885 A
european eMc Directive no. 2004/108/ec (15/12/2004)
lv Directive no. 2006/95/ec Dated 12 December 2006
iec 62053-21 / iec 62052-11
Single phase 2 wires 230v / two phase 2 wires 400v
three phase 3 wires 3x230 v / 3x400 v and three phase 4 wires
3x230/400 v
Detection of cabling error
50 and 60 Hz (± 5 Hz)
autosupplied
< 10 va or 2 W
< 1.0 va
10 ma
50 ma
250 ma
5 a
6 a
120 a for 0.5 s (en50470-3 and iec 62053-21)
230 v ac Phase/neutral 400 v ac Phase/Phase ± 15%
230 / 400 v ac + 15%
yes
no*
0.1 kW
yes
yes
yes (0 to 999999.9 kWh)
yes
1 kWh
class 1 (iec 62053-21)
yes*
4*
no*
10000 impulses / kWh
red
7 Digit leD with blue back-lighting
1 s
30 s
cf. table below