6.4. Wiring of main power supply and equipment capacity
A
B
208/230 VAC
60 Hz
A : Switch (Breakers for Wiring and Current Leakage)
B : Outdoor nit
C : Pull Box
D : Indoor nit
Thickness of Wire for Main Power Supply and On/Off Capacities
Model
Outdoor Unit
P36/48
Indoor Unit
*1. A breaker with at least 3.0 mm [1/8 inch] contact separation in each poles shall be provided. Use non-fuse breaker ( F) or earth leakage breaker ( V).
Total operating current of the indoor unit
F0 = 15 A or less *2
F0 = 20 A or less *2
F0 = 30 A or less *2
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + {V1 × (Quantity of Others)/C}