Wiring Of Main Power Supply And Equipment Capacity - Mitsubishi Electric CITY MULTI PUMY-P100VHMB Manuel D'installation

Masquer les pouces Voir aussi pour CITY MULTI PUMY-P100VHMB:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 24
6. Electrical work
I M-NET Remote Controller
OC
(51)
TB3
C or D
M1M2 S
M1 M2 S
TB7
G
(101)
L
OC
3
(53)
TB3
C or D
M1M2 S
M1 M2 S
TB7
Power Supply
Unit
M1M2S
G-50A
M1M2 S
Fig. 6-2
A : Group 1
B : Group 3
C : Screw on the electrical component box
D : Screw on the electrical component box

6.4. Wiring of main power supply and equipment capacity

Schematic Drawing of Wiring (Example) (Fig. 6-4)
A
~/N 220/230/240 V 50 Hz
~/N 220 V 60 Hz
A : Switch (Breakers for Wiring and Current Leakage)
B : Outdoor Unit
C : Pull Box
D : Indoor Unit
Thickness of Wire for Main Power Supply and On/Off Capacities
Model
~/N 220/230/240 V 50 Hz
Outdoor Unit
P100-140
~/N 220 V 60 Hz *2
~/N 220/230/240 V 50 Hz
Indoor Unit
*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Max. Permissive System Impedance 0.22 (Ω)
1. Use a separate power supply for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57). For
example, use wiring such as YZW.
6. Install an earth longer than other cables.
Warning:
• Be sure to use specified wires to connect so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause heating
or fire.
• Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
• Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of
unit or fire.
IMPORTANT
Make sure that the current leakage breaker is one compatible with higher harmonics.
Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of inverter.
L
1
A
F
IC
IC
IC
(01)
(02)
(05)
TB5
TB5
TB5
M1 M2 S
M1 M2 S
M1 M2 S
r
3
A B
A B
A B
(105)
(155)
RC
RC
RC
E
L
4
IC
IC
IC
(04)
(07)
(03)
TB5
TB5
TB5
M1 M2 S
M1 M2 S
M1 M2 S
A B
(104)
RC
B
E : Sub Remote Controller
F : Group 5
G : Shielded Wire
( ): Address
B
~/N 220/230/240 V 50 Hz
~/N 220 V 60 Hz
Minimum Wire Thickness (mm
Power Supply
Main Cable
5.5 (6)
1.5
~/N 220 V 60 Hz
I MA Remote Controller
OC
IC
(51)
(06)
TB3
TB5
C or D
M1 M2 S
M1M2 S
M1 M2 S
TB7
G
OC
(53)
TB3
C or D
M1M2 S
M1 M2 S
TB7
Power Supply
Unit
M1M2
S
G-50A
M1M2
S
A
D
Fig. 6-4
2
)
Breaker for
Branch
Ground
Wiring*1
5.5 (6)
1.5
1.5
L
1
A
IC
IC
c
2
(01)
(02)
TB5
TB15
TB5
TB15
M1 M2
S
1 2
M1 M2 S
1 2
A B
MA
L
L
3
4
IC
IC
(04)
(03)
TB5
TB15
TB5
TB15
1 2
M1 M2 S
1 2
M1 M2 S
A B
MA
B
Fig. 6-3
C
D
D
Breaker for Current Leakage
32 A
32 A 30 mA 0.1 sec. or less
15 A
15 A 30 mA 0.1 sec. or less
F
IC
IC
c
2
(05)
(06)
TB5
TB15
TB5
TB15
M1 M2 S
1 2
M1 M2 S
1 2
c
4
A B
A B
MA
MA
E
IC
(07)
TB5
TB15
1 2
M1 M2 S
D
11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

City multi pumy-p125vhmbCity multi pumy-p140vhmb

Table des Matières