After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power sup-
ply or control wiring, wrong polarity, and no disconnection of one phase
in the supply.
Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
Warning:
Insulation resistance
After installation or after the power source to the unit has been cut for an extended
period, the insulation resistance will drop below 1 M due to refrigerant accumulat-
ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance
of the compressor.
2. If the insulation resistance is below 1 M , the compressor is faulty or the resist-
ance dropped due the accumulation of refrigerant in the compressor.
3. After connecting the wires to the compressor, the compressor will start to warm
up after power is supplied. After supplying power for the times indicated below,
measure the insulation resistance again.
Refer to the indoor unit installation manual.
Be sure to perform the test run for each indoor unit. Make sure each indoor
unit operates properly following the installation manual attached to the unit.
If you perform the test run for all indoor units at once, you cannot detect any
erroneous connection, if any, of the refrigerant pipes and the connecting
wires.
* The compressor operation is not available for 3 minutes at least after the
power is supplied.
The compressor can emit noise just after turn on the power supply or in case
of low outside air temperature.
About the restart protective mechanism
Once the compressor stops, the restart preventive device operates so the compressor
will not operate for 3 minutes to protect the air conditioner.
Perform the following procedures to collect the refrigerant when moving the
indoor unit or the outdoor unit.
1 Turn off the circuit breaker.
2 Connect the low pressure side of the gauge manifold to the service port of the
gas side stop valve.
3 Close the liquid stop valve.
4 Supply power (circuit breaker).
* Start-up of the indoor-outdoor communication takes about 3 minutes after the
power (circuit breaker) is turned on. Start the pump-down operation 3 to 4
minutes after the power (circuit breaker) is turned O .
5 Perform the test run for cooling operation (SW3-1: O
compressor (outdoor unit) and ventilators (indoor and outdoor units) start operating
and test run for cooling operation begins. After the cooling operation has been
carried out for approximately ve minutes, set the outdoor service switch SW2-4
(pump down switch) from OFF to O .
* Do not continue to operate for a long time with the switch SW2-4 set to O .
Make sure to switch it to OFF after pump down is completed.
* Only set the SW3-1 and SW3-2 to O if the unit is stopped. However, even if the
unit is stopped and the SW3-1 and SW3-2 are set to O less than 3 minutes after
the compressor stops, the refrigerant collecting operation cannot be performed.
Wait until compressor has been stopped for 3 minutes and then set the SW3-1
and SW3-2 to O again.
14
The insulation resistance drops due to accumulation of refrigerant in the
compressor. The resistance will rise above 1 M after the compressor is
warmed up for 12 hours.
(The time necessary to warm up the compressor varies according to atmos-
pheric conditions and refrigerant accumulation.)
To operate the compressor with refrigerant accumulated in the compressor,
the compressor must be warmed up at least 12 hours to prevent breakdown.
4. If the insulation resistance rises above 1 M , the compressor is not faulty.
Caution:
The compressor will not operate unless the power supply phase connec-
tion is correct.
- Starting operation immediately after turning on the main power switch can result
in severe damage to internal parts. eep the power switch turned on during the
operational season.
The followings must be checked as well.
The outdoor unit is not faulty. LED on the control board of the outdoor unit ash
when the outdoor unit is faulty.
Both the gas and liquid stop valves are completely open.
Note:
In case of the test run from outdoor unit, all indoor units operate. Therefore,
you can not detect any erroneous connection of refrigerant pipes and the
connecting wires. If it aims at detection of any erroneous connection, be sure
remote controller".
SW3-1
SW3-1
* After performing the test run, set SW3-1 to OFF.
A few seconds after the compressor starts, a clanging noise may be heard from
the inside of the outdoor unit. The noise is coming from the check valve due to
the small difference in pressure in the pipes. The unit is not faulty.
the test run. (To change the test run operation mode during the test run, stop
the test run by DIP switch SW3-1. After changing the test run operation mode,
resume the test run by switch SW3-1.)
6 Fully close the gas stop valve when the pressure reading on the gauge drops
7.1 - 0.0 PSIG (approximately 0.5 - 0.0 kgf/cm
7 Stop the air conditioner operation (SW3-1: OFF and SW3-2: OFF). Set the outdoor
service switch SW2-4 from O to OFF.
8 Turn off the power supply (circuit breaker).
* If too much refrigerant has been added to the air conditioner system, the
pressure may not drop to 7.1 PSIG (0.5 kgf/cm
ant collecting device to collect all of the refrigerant in the system, and then
recharge the system with the correct amount of refrigerant after the indoor and
outdoor units have been relocated.
and SW3-2: OFF). The
Warning:
When pumping down the refrigerant, stop the compressor before discon-
necting the refrigerant pipes. The compressor may burst and cause injury if
any foreign substance, such as air, enters the system.
ON
Cooling operation
OFF
ON
ON
2
)
2
). If this occurs, use a refriger-