Turbine gas meter Instruction Manual
Intended Use and Field of Application
This product is intended for :
calibratable volumetric metering using SM-RI-X turbine meters and for non-
calibratable volumetric metering using the Q-75 turbine meter of
- flammable gases
- non-flammable gases
and is suited for use in potentially explosive atmospheres of
Category 2(Zone 1) of Class EX ll 2 G c llC T4
Other fields of application/media on request.
This product is not intended for :
for metering aggressive gases, oxygen and acetylene.
Legal Declarations
Declarations of Conformity: see Annex C
Period of validity of calibration: this is based on the regulations of the country
concerned, where the turbine gas meter will be used
Staff
These Instructions are aimed at staff who have adequate specialist and technical
knowledge on the basis of their training and experience in the sector of energy
and gas distribution.
Incorrect use can be fatal!
Operating Location
The minimum length of the inlet section for SM-RI-X must be at least twice the
nominal diameter for reasons relating to measurement accuracy.
An inlet section of ≥ 5 x DN is required for Q-75.
The inlet section must be designed as a straight pipe section with the same
nominal diameter as the meter.
The length of the outlet section is at least 1 x DN of the same nominal diameter.
The flow through the meter must be free of vibrations/pulsations in order to
avoid measuring errors.
The gas may not contain suspended particles > 50 μm.