In Operation

Installation / Connection

Before installation please ensure that
- the protective caps or plastic sheeting's are removed.
- the meter and accessories have been inspected for transport damage.
- the accessories have been checked for completeness.
- the line is free of obstacles and pollution.
You will require the following items for installation:
- suitable gaskets for the relevant gases.
The following gaskets, among others, are suitable:
 flat seals,
 spiral-wound gaskets
 grooved seals and gaskets.
 Nuts, stud bolts or hexagon screws according the flange directive.
Then install the meter:
 preferably in horizontal position with index at the top.
If you wish to install the unit vertically and if an oil pump is present, the oil
pump must also be fitted vertically.
 only in flow direction,
 stress-relieved,
 with the supplied accessories,
 gas-tight,
When fitting the gaskets, ensure that they are aligned concentrically and do not
project into the flow channel.