INSTALLATION INSTRUCTIONS
Step 1 - Preparation (cont.)
C. Install the Leak Sensor.
Step 1: Find the bracket and remove it from the unit.
Leak sensor bracket is pre-installed on the backside of the unit, please find it and remove it from the unit.
Step 2: Attach the leak sensor into the bracket. (Be sure to use the provided flat screw.)
Step 3: Connect the leak sensor to the unit PCB.
Remove the electrical box cover and route the refrigerant leak sensor wire from the back of the unit, pull the
PCB out and connect the refrigerant leak sensor to port CN3 on the PCB. Please ensure to route the wire for the
refrigerant leak sensor from the back of the high wall to the front, under the electrical box. Please also organize
any loose wire so that it doesn't prevent the install of the electrical box cover.
Step 4: Install the bracket with the sensor back to the original location.
14
Leak Sensor
Connect to
CN3 on PCB
Remove
this
screw
Remove this
screw and
take PCB out
Use
provided
screw to
install
CN1: Reserved
for wired
controller
connection.
CN3 is this
connector
31-5001074 Rev. 0