02910
INSTALLER/USER QUICK GUIDE
Electronic touchscreen timer-thermostat for ambient temperature control (heating
and air-conditioning), designed to display energy data via an energy meter, class I
temperature control device (contribution 1%) in ON/OFF mode, class IV (contribu-
tion 2%) in PID mode, 1 programmable multifunction input, change-over relay output
5(2) A 230 V~, powered by batteries AA LR6 1.5 V (not supplied), wall mounting.
FEATURES.
• Rated supply voltage: 2 alkaline batteries AA LR6 1.5 V
• Operating temperature range: 0-40°C (-T40)
• Temp. measurement accuracy (built-in probe): 0.5°C between +15°C and 30°C, 0.8°C at the ends.
• Relay output with clean change-over contacts: 5(2) A 230 V~
• Terminals: Relay C, Relay NC, Relay NO, 2 for multi-purpose inlet
• Configurable in Heating/Air-Conditioning mode (winter/summer)
• Temperature control algorithms: ON/OFF or PID selectable via user interface.
• Operating modes: Off, Antifreeze (heating only), Away, Manual, Automatic, Timed Manual.
• 6 settable temperature set-point/offset (economy, comfort, manual, away, antifreeze, reduction).
• Restriction on local interface access via PIN and configurable multi-function input.
• Communication with energy probe 02960 via additional card 02915 to be installed on the
timer-thermostat base for reading and displaying energy data (power, energy).
• Protection class: IP20.
• Action type: 1.B; Pollution class: 2 (normal); Rated pulse voltage: 4000 V.
• ErP classification (Reg. EU 811/2013): ON/OFF: class I, contribution 1%; PID: class IV, contribution 2%.
IMPORTANT: In order to avoid any accidental modifications, first press and hold down the
required icon displayed to enable the function.
MAIN SETTINGS.
Tap
and then, using
and
confirm with
.
AUTO Operating mode selection
Using
and
, select
or AUTO or
MANUAL operation setting
Using
and
set the desired temperature and confirm with
ANTIFREEZE
Select
to set the Antifreeze temperature (to protect the pipes).
Switching OFF
Select OFF and the timer-thermostat will switch off and no longer make any adjustments.
Setting the time and date
Using
and
set the time, confirm with
then the day of the week. The days of the week are represented by 1 to 7.
Selecting heating/air-conditioning
Using
and
, select
or
Setting units of measurement
Using
and
,select °C or °F and confirm with
AUTO operation setting
As soon as you enter the menu, the display shows a flashing dash for the day to which the
current programming refers.
1. Using
and
select the day to program and confirm with
2. Using
and
select the temperature to be associated with the current time
(which is shown on the clock). This temperature, highlighted by the blinking, can be selected
from:
: Away temperature (T away)
: Economy temperature (T economy)
: Comfort temperature (T comfort)
The 3 "dashes" blinking indicate the time slot that you are setting. The selected temperature will
be applied beginning at the indicated time for all of the next quarter of an hour.
3. Tap
to assign the temperature you have just set to the following fifteen minutes too.
4. Using
and
move respectively between the hours of the day and move forwards
or backwards 15 minutes at a time; with
Programming ends when the temperatures have been set for all the hours of the day and the
clock displays the time 23:45. Tap
5. Using
and
, sselect:
: to copy the entire time program for the current day onto the next day.
: to programme the next day without making a copy of the day you have just set
: to finish programming.
Tap
to confirm.
49400593C0 01 1809
, select the desired menu (blinking icon) and
or OFF and confirm with
.
and similarly set the minutes and
and confirm with
.
.
.
and
set the desired temperature.
to confirm.
When operating in AUTO mode, tap
other than the one associated with the current time slot. Confirm with
into TIMED MANUAL mode.
TIMED MANUAL operation setting
1. Using
and
2. Using
and
maintained and confirm with
At the end of the set time you go back into AUTO mode, the
AUTO reappears.
Temperature settings
Using
,
,
1.
and
: Away temperature (T away)
2.
and
: Economy temperature (T economy)
3.
and
: Comfort temperature (T comfort)
4.
: temperature differential of the device (only if in OnOff adjustment mode)
5.
and
: thermal delta in remote reduction mode (if enabled)
6.
and
: "antifreeze" mode temperature (only if in "heating" mode)
Setting the password
Using
and
set the digits of the PIN one at a time and confirm each digit with
.
Setting the PIN to "000" gives free access to the device (equivalent to not setting the
password).
N.B. To reset the device (restoring the parameters to their default values) or the PIN, switch
off the timer-thermostat and remove the batteries, then replace them and switch back on; for
about 3 secs., the display will indicate the firmware version and the icon
.
within 3 s and select rSEt and YES using and
FOR THE INSTALLER.
For further information and for details on all the other timer-thermostat menus please
refer to the installer manual that can be downloaded from the website www.vimar.com.
FOR THE USER.
Before using the timer-thermostat please consult the user manual that can be down-
loaded from the website www.vimar.com. Keep this documentation for future reference.
INSTALLATION RULES.
Installation should be carried out by qualified staff in compliance with the current regulations
regarding the installation of electrical equipment in the country where the products are installed.
CHANGING BATTERIES.
Remove the front by inserting a screwdriver in the grooves on the lower side and replace the
batteries, respecting the polarity indicated (see relative figures).
• away
icon battery charged
• flashing
icon battery almost flat (replace it)
• fixed on
icon battery flat (the device will go OFF and it is no longer possible to
switch to operation).
REGULATORY COMPLIANCE.
LV directive. EMC directive.
Standards EN 60730-2-7, EN 60730-2-9.
WEEE - User information
If the crossed-out bin symbol appears on the equipment or packaging, this means
the product must not be included with other general waste at the end of its wor-
king life. The user must take the worn product to a sorted waste center, or return it
to the retailer when purchasing a new one. Products for disposal can be consigned
free of charge (without any new purchase obligation) to retailers with a sales area of
at least 400 m
, if they measure less than 25 cm. An efficient sorted waste collec-
2
tion for the environmentally friendly disposal of the used device, or its subsequent
recycling, helps avoid the potential negative effects on the environment and people's
health, and encourages the re-use and/or recycling of the construction materials.
and
to set the temperature to a value
set the desired temperature and confirm with
set the time for which the temperature you have just set is to be
.
and
and confirm to
set:
,
and
36063 Marostica VI - Italy
and you go
.
icon switches off and
.Touch
.
Viale Vicenza, 14
www.vimar.com