Preparing the mains socket
Undo the screw.
1.
→ Fig.
15
Use a screwdriver to lift the strain relief.
2.
→ Fig.
16
Loosen the strain relief.
3.
→ Fig.
17
Connecting the cable to the mains socket
For 3 N, connect the cable to the mains socket in
1.
accordance with the following figure.
→ Fig.
18
For 2 N, connect the cable to the mains socket in
2.
accordance with the following figure.
→ Fig.
19
For 1 N, connect the cable to the mains socket in
3.
accordance with the following figure.
→ Fig.
20
For 2 L/2 N, connect the cable to the mains
4.
socket in accordance with the following figure.
→ Fig.
21
Note the colours of the cables.
5.
– BN: Brown
– BU: Blue
– GN/YE: Yellow and green
– BK: Black
– GY: Grey
If required, install the enclosed copper bridges in
6.
accordance with the connection diagram.
Connect the cables and then tighten the screws of
7.
the mains socket.
For a 1 N~ or 2 L/2 N connection in accordance
8.
with the connection diagram, 1 corresponds to the
fan motor.
For a 2 N~/3 N~ connection, phase L1 (grey) cor-
9.
responds to the fan motor.
Secure the cable in the mains socket
Use the strain relief to secure the power cable in
1.
place.
Tighten the screw at the correct position.
2.
Do not use a cordless screwdriver.
‒
→ Fig.
22
To facilitate closing the mains socket, arrange the
3.
cables in the central area of the mains socket.
Close the cover on the mains socket.
4.
Instructions for the exhaust air pipe
The appliance manufacturer does not provide any
warranty for faults attributable to the pipeline.
¡ Use a short, straight exhaust air pipe with as large
a pipe diameter as possible.
¡ Long, rough exhaust air pipes, many pipe bends
or small pipe diameters reduce the suction power
and increase the fan noise.
¡ Use an exhaust air pipe that is made of non-com-
bustible material.
¡ To prevent condensate from returning, fit the ex-
haust pipe with a 1° gradient from the appliance.
Flat ducts
Use flat ducts with an inner cross-section that corres-
ponds to the diameter of the round pipes:
¡ Diameter of 150 mm corresponds to ap-
prox. 177 cm².
¡ Use sealing strips for different pipe diameters.
¡ Do not use any flat ducts with sharp bends.
Round pipes
Round pipes with an inner diameter of 150 mm.
Instructions for the air extraction mode
For air extraction mode, a one-way flap should be in-
stalled.
Notes
¡ If a one-way flap is not included with the appli-
ance, one can be ordered from a specialist re-
tailer.
¡ If the exhaust air is conveyed through the external
wall, a telescopic duct should be used.
Checking the units
Check whether the fitted unit is level and has suffi-
1.
cient load-bearing capacity.
The maximum weight of the appliance is approx.
25 kg.
The worktop into which you are fitting the appli-
ance must be able to withstand loads of approx.
60 kg.
Ensure that the stability of the fitted unit is also
2.
guaranteed following cut-out work.
Use suitable substructures to ensure the load-
3.
bearing capacity and stability, particularly in the
case of thin worktops.
Take the appliance weight, including additional
‒
load, into consideration.
Use heat-resistant and moisture-resistant rein-
‒
forcement material.
Ensure that the fitted unit is heat-resistant up to
4.
90 °C.
Do not support any other appliances, e.g. ovens,
5.
refrigerators, dishwashers or washing machines.
Only check that the appliance is level once it has
6.
been installed in the installation opening.
You can freely select the clearance to a top cab-
7.
inet. In doing so, take into consideration the ease
of use and ergonomics when using the plate.
Preparing the units
Requirement: The fitted units are heat-resistant up to
90 °C.
Mark the unit cut-out in accordance with the in-
1.
stallation diagram.
→ Fig.
13
Drill four holes with a diameter of 6 mm.
2.
→ Fig.
23
Ensure that the angle of the cut surface to the
3.
worktop is 90°.
→ Fig.
23
Observing the minimum clearances when in-
stalling above a drawer
When removing the overflow container on integ-
1.
rated appliances, take the minimum clearances
into consideration.
→ Fig.
10
Observe the position of the overflow container.
2.
→ Fig.
11
Preparing the unit for circulating-air mode with the
adapter
Notes
¡ We do not recommend to install on a non-
thermally insulated outer wall or above a cold floor
(µ ≥ 0.5 W/m² °C).
¡ Air outlets must not be directed at other appli-
ances, they should be parted by a separation
panel. If you cannot install any separation panels,
refer to other installation types..
21