PROGRAMMING
Load shedding configuration
LS variable allows associated LS timer configuration.
LS
Output
Associated funciton
O1 to O2
LS
* In case of DTT variable configuration below LS, LS will be automatically set to to DTT value.
Example: load shedding configuration
>
Step 1: Press "right" push button to make first variable blinking (LS)
>
Step 2: press push buttons "top" and "bottom" to modify the
variable
>
Step 3: Press "validation"
>
Step 4: Press "bottom" push button to access timer
value configuration
44
Setting range
Default value
0 to 60 s (≤ DTT)*
2
CONTROL AND TEST MODES
It is possible to start test sequences or to control electrically the changeover system from keypad.
Enter Control or Test modes
>
Step 1: Press "mode" push button to make test or control led blinking
>
Step 2: Press "validation" push button to make control or test led become fixed
Control Mode
Access code is displayed directly
Test Mode
>
It is possible to test leds and LCD without entering any code by pressing directly
>
Test on load or test off load access codes are displayed after pressing
or
>
Enter the code 4000 using "left", "right", "top" and "bottom" push buttons
>
Press "validation" push button to enter
Exit control or test modes
>
Press "ESC" push button
The new operational mode (automatic or manual) depends on information from master.
Control or Test modes use
>
Direct access by pressing
and
>
To start a test (off load or on load) or to control the changeover switch electrically, press
,
and
45