Télécharger Imprimer la page

Tripp-Lite SmartPro 1U Manuel Du Propriétaire page 12

Publicité

Specifications
Model
Nominal input voltage(s)
and range
Nominal input frequency
and tolerance
Nominal output voltage
Nominal output fre-
quency
Output voltage regula-
tion in line-mode
Output voltage regula-
tion in battery mode
Nominal output power
in W / VA:
Output voltage wave-
form
Maximum output
current @ P .F.
Efficiency with nominal
load
Maximum operating
altitude at 100% of
nominal power
Online overload capabil-
ity
Overload capacity in
battery mode
Current limitation
Autonomy time at full
load
Battery recharge time
Transfer time
Outlets
Maximum input current
21-10-019-933903-Book.indb 12
21-10-019-933903-Book.indb 12
SMX500RT1U
230V~, 187-265V~
50/60 Hz (+/- 5 Hz)
230V~ sinusoidal in line mode
and 230V~ PWM in battery mode
50/60 Hz (+/-0.5 Hz)
230 V~ (+15% / - 8%)
230V~ (+/-5%)
300W / 500VA
Sinusoidal in line mode and
quasi-sine (PWM) in battery mode
2.17A @ 230V~
P .F. = 0.6
97%
6561 ft. (2000 m)
above sea level
120% @ 5 minutes
120% @ 5 minutes
Input 7A
3 minutes @ 300W
12 hours
2 milliseconds typical
(4 milliseconds max)
5x C13 outlets with battery
backup, regulation and surge;
1x C13 outlets only for surges
7A
12
SMART500RT1U
120V~, 90-139V~
60 Hz (+/- 5 Hz)
120V~ sinusoidal in line mode
and 120V~ PWM in battery mode
60 Hz (+/-0.5 Hz)
120 V~ (+16% / - 14%)
120V~ (+/-5%)
300W / 500VA
Sinusoidal in line mode and
quasi-sine (PWM) in battery mode
4.2A @ 120V~
P .F. = 0.6
97%
6561 ft. (2000 m)
above sea level
120% @ 5 minutes
120% @ 5 minutes
Input 10A
3 minutes @ 300W
12 hours
6 milliseconds typical
(10 milliseconds max)
5x 5-15R outlets with battery
backup, regulation and surge;
1x 5-15R outlets only for surges
10A
10/14/2021 3:37:48 PM
10/14/2021 3:37:48 PM

Publicité

loading

Ce manuel est également adapté pour:

Smartpro smx500rt1uSmartpro smart500rt1uAg-03adAg-03aa