3
Function
Connected sensors with a terminating resistor of 8.2 kOhm are monito-
red for a change in current.
In the idle mode
• all safety outputs are conductive
• the LED lights up green
• both dots on the display flash
When one or more sensors are actuated
• the total resistance of the sensor system drops towards zero ohm
• the defined switching threshold is not reached anymore
• the corresponding Safety output opens
• the LED lights up orange, P appears on the display
In the event of a fault in the sensor circuit (for example cable breakage)
• the total resistance of the sensor system increases
• the defined switching threshold is exceeded
• both Safety outputs open
• the LED lights up red, E appears on the display
4
Configuration and set-up
4.1
Terminals
Wiring the device
4.2
Switch on supply voltage
If necessary, configure the device
4.3
Configuration mode (edit mode)
To enter Configuration menu (see also chapter 4.4):
• Enter diagnostic menu: Press "Mode" and "Data" buttons simultaneously for 2 seconds → Status LED flashes orange.
• Press "Mode" repeatedly until "C" and "con" are displayed.
• Press "Data" button, "con" starts flashing.
• Press "Mode" and "Data" buttons simultaneously until "con" stops flashing.
• Release "Mode" and "Data", "C" starts flashing, both safety outputs open.
{
C
h
2 sec
Configu-
Holding
ration
time
001*
001
Sensor 1 + 2
none
002
002
Sensor 1
100 ms
003
003*
Sensor 2
200 ms
004
500 ms
005
1 s
* Factory setting
On initial commissioning, the device must be adapted (configured)
to the application.
Configuration
• Press the "Mode" button to select the requested parameter.
• Press the "Data" button to set the value.
Exit Configuration menu:
Press "Mode" until "h End", than press "Data".
2
A1 / A2: ▲ Supply voltage (24 V DC or 24 V AC)
1 / 2:
Sensor 1
3 / 4:
Sensor 2
11 / 14: ▲ Safety output 1
21 / 24: ▲ Safety output 2
5 / 6:
Status output (see chapter 4.5)
No function test possible without connected outputs (Display E 007 or E 008)
i
▲ Wiring mandatory
h
End
Exit
Configuration
menu
Block diagram
1
Sensor 1
8k2
2
T1
T2
1
3
Sensor 2
8k2
4
1
2
A1
24 V AC/DC
A2
Adjustable parameters:
C active inputs: 001 = both inputs 1 and 2, 002 = only input 1,
003 only input 2
h The holding time (extension of the output signal):
001 = none, 002 =100 ms, 003 = 200 ms, 004 = 500 ms, 005 = 1000 ms
14
Safety
Function and
Output 1
safety check
11
24
Safety
Function and
Output 2
21
safety check
5
Status
6
Output
(see
chapter 4.5)
Power supply