3.3 Warning
•
Warning! All electrical connections must be performed by professionals in accordance with local regulations. Ensure
that the machine is connected to the correct voltage and frequency as specified on the machine's nameplate.
•
Warning! The power supply switch should only be used for emergency shutdowns. When the machine stops, the
regeneration blower also stops. If the regeneration heater accumulates heat, it may cause damage to components
similar to the heater.
•
Warning! The dehumidifier is designed for a specific air processing volume and should not be directly connected to
an air conditioning system. Improper adjustment of the treated air and regenerated air volumes can lead to
equipment failure.
3.4 Handling Equipment
Each module of the dehumidification machine weighs 15 kg, so it is essential to use a lifting device to prevent
injury to personnel and damage to the machine. Handle the dehumidification machine with care. A crane or forklift
can be used to move the machine. When using a crane, select appropriate lifting points that do not come into
contact with the motor, control system, or exposed pipe fittings to avoid damaging the machine. Forklift and crane
holes are located in the lower part of each module for this purpose.
3.5 Safety Placement
his dehumidifier is designed for indoor installation, and it is crucial to maintain adequate and compact service
space for cleaning and maintenance. To prevent internal condensation, the dehumidifier should not be exposed to
environments where the temperature is lower than the dew point of the processing air. If the machine must be
installed outdoors, appropriate protective measures should be taken to prevent rainwater or snow from entering the
unit.
3.6 Foundation Setting
The dehumidification machine must be installed on a horizontal surface or platform that can support the
machine's weight. A special foundation is not necessary if the maximum load capacity is not exceeded. After
installing the dehumidifier, verify that it is level. If the unit is required to be fixed setting, the installation hole
shall be prefabricated on the steel of the unit.
3.7 Air Duct Connection
The processing air and regenerated air ducts should adhere to the recommended values specified in ISO 7807. The
installation of pipe fittings for ducts and elbow flanges should not exceed 20mm in length. When installing the
connected pipes for the dehumidifier's inlet and outlet, please consider the following recommendations:
•
Minimize the length of the pipe as much as possible to reduce static pressure loss in the air system.
EN