Concrete Slab
At the appropriate location, construct a concrete slab:
10.13"
7"
19"
9.5"
B
59"
C
D
E
Slab Top VIew
• 28 day compression strength of 3000 psi (200 MPa)
• Minimum 5 inches thick
• Minimum 6 inches wider than enclosure on all sides
(shown as dashed line (D))
• Strengthen slab with No. 6 reinforcing bars (on
12" centers) or 8 ga. steel wire fabric (6" centers).
NOTE: Avoid placing reinforcement in entrance
stub-up area.
Attach unit to slab at four corner locations (A) with
minimum 5/16" diameter (8mm) masonry anchor bolts long
enough to secure the unit.
The fuel inlet location (C) and the exhaust opening (E) are
shown for reference.
Electrical and Fuel Inlet Locations
A through-slab power cable stub-up is preferred (see
figure above). If stub-up's are not used, (F) indicates the
recommended location for punching holes for attaching
power conduit. The 1 inch N.P.T. fuel inlet connector (C) is
shown for reference.
49"
7.38"
34.25"
8"
a
92"
108"
F
Lifting the Generator
The generator weighs more than 2,075 pounds (941 kg).
Proper tools, equipment and qualified personnel should be
used in all phases of handling and moving the generator.
WaRNING
Hazardous Voltage
Contact with power lines can cause electric
shock or burn.
Lifting Hazard / Heavy Object
Can cause muscle strain or back injury.
•
DO NOT contact any power lines when using required
lifting/hoisting equipment.
•
DO NOT lift or move generator without assistance.
•
Use lifting pipes or straps. The unit may shift during
movement, which can cause injury.
•
DO NOT lift unit by roof as damage to generator
will occur.
Two 60" lengths of 2" Schedule 40 pipe (G), supplied by the
installer, are required to lift the generator onto cement pad.
Insert pipes through the lifting holes (H) located near the
unit's base.
H
Use a spreader bar to ensure that the chains, straps or
cables DO NOT touch the generator's roof.
C
G
9