05
Connect the unit to the hydronic system by using the indicated inlet/outlet connections. Make sure the connections are airtight - use a
sealant. The heat exchanger comes with a supplied air vent and sealing plug.
If the unit is used for cooling, the hydronic pipes must be insulated.
When using devices for cooling: iron couplings prohibited.
06
Install the condensate trap.
07
Non-condensing cooling - close the drain pipe of the condensate
trap (02cm).
Incorrect installation and failure to follow the instructions can lead to severe water damage.Perform maintenance according
to the intensity of use and the installation environment.Therefore, Jaga N.V. shall not be liable for any consequential damage
whatsoever.Read these instructions carefully.
64
Air vent
Condensing cooling - pre-assembled condensate pump with
breaker point (class I device)
JAGA NV | BRIZA S - BMS | MANUEL | 30.09.2024 | V.1.05
Use a back wrench when fastening the
hydronic connections!
Remove black plug at hydronic con-
nection.
OPTION
Only in combination with a 230 VAC connection with
watertight power supply!