Technical data
inverter
nx3 rack 16000-48 st
Continuous Power
15000 VA
Power 30min
16000 VA
Power 5sec
30000 VA
230V Phase to Neutral /
AC output voltage
400V Phase to Phase
AC output frequency
50/60Hz
solar
Solar MPPT inputs
2
PV input voltage
100 – 900 Vdc
PV startup voltage
200 Vdc
PV max current
2 x 27 Adc
PV power
2 x 8 kW
transfer
Max rated current
3 x 80 Aac
Phase to neutral
230 Vac
voltage
Phase to phase
400 Vac
voltage
Frequency
50/60 Hz
14
Battery nominal voltage
48Vdc (38-68Vdc)
Battery charge current
300 Adc
Maintenance and recycling
IP 30
Maintenance and recycling
EN
Except for the periodic check of the connections (tightening, general
Protection
condition), the next does not require any particular maintenance. To
Class I
dispose of this product, please use the service for the collection of
electrical waste and observe all obligations in force in the place of
purchase.
Entretien et recyclage
FR
À l'exception du contrôle périodique des branchements (serrage, état
général), le next ne nécessite pas d'entretien particulier. Pour vous
débarrasser de ce produit, veuillez utiliser les services de collecte des
déchets électriques et observer toutes les obligations en vigueur selon le
lieu d'achat.
Wartung und Recycling
DE
Abgesehen von der regelmäßigen Kontrolle der Anschlüsse
(Fixierung, allgemeiner Zustand) bedarf der next keinerlei besonderer
Wartungsarbeiten. Beachten Sie bei der Entsorgung dieses Gerätes die
geltenden örtlichen Vorschriften und nutzen Sie die Sammeldienste/-
stellen für Elektro-/Elektronik-Altgeräte.
Mantenimiento y reciclaje
ES
A excepción del control periódico de las conexiones (apriete, estado
general), el next no requiere un mantenimiento particular. Para la
eliminación del producto, acuda a los servicios de recogida de residuos
eléctricos y cumpla todas las obligaciones vigentes en el lugar de compra.

Publicité

loading