Ensure that the equipment is used under the correct ambient conditions. Never operate the
product in a wet or dusty environment. Ensure there is adequate free space for ventilation
around the product and check that the ventilation vents are not blocked.
Ensure that the required system voltage does not exceed the product's capacity.
Transport and Storage
Ensure that the mains power and battery cables have been disconnected before storing or
transporting the product.
No liability can be accepted for any transport damage if the equipment is shipped in non-original
packaging.
Store the product in a dry environment; the storage temperature must be between -40 °C and
60 °C.
Consult the battery manufacturer's manual in respect of transport, storage, charging, recharging
and disposal of the battery.
2. DESCRIPTION
2.1 General
All-in-one solar power solution
The EasySolar combines a MPPT solar charge controller, an inverter/charger and AC
distribution in one enclosure.
The product is easy to install, with a minimum of wiring.
Solar charge controller: SmartSolar MPPT 100/50
Up to three strings of PV panels can be connected with three sets of MC4 (PV-ST01) PV
connectors.
Inverter/charger: MultiPlus Compact 12/1600/70 or 24/1600/40
The MPPT charge controller and the MultiPlus inverter/charger share the DC battery cables
(included). The batteries can be charged with solar power (MPPT) and/or with AC power
(inverter/charger) from the utility grid or a genset.
AC distribution
The AC distribution consists of a RCD (30 mA/16 A) and four AC outputs protected by two 10 A
and two 16 A circuit breakers.
One 16 A output is controlled by the AC input: it will switch on only when AC is available.
PowerAssist
Unique PowerAssist technology protects the utility or generator supply from being overloaded
by adding extra inverter power when needed.
2