V minimum and V maximum (DC fan voltage). These system functions allow fan speeds to
be adjusted according to the voltage specifications of the indoor unit manufacturer.
Basic mode. This allows you to activate the thermostat's basic mode.
Autochange mode. Allows the system's mode to be changed automatically based on the
temperature measured in production.
EN
Note: Autochange Mode can only be activated if the system is configured as 2 pipes and
has a battery probe.
Cooling mode/Heating mode:
Lowest temp./Highest temp. These allow you to select the maximum temperature for
heating mode (19-30°C, by default: 30°C) and the minimum temperature for cooling mode
(18-26°C, by default: 18°C), in steps of 1°C. If you want, you can disable any of the modes.
Cooling battery temperature/Heating battery temperature. These allow you to configure
the temperature limit values of the cooling and heating batteries if they are installed on
output AI2 (2-pipe installation) or AI2 and AI3 (4-pipe installation). They will be used as a
reference for automatic mode changeover, fan management and control of the minimum
opening of the proportional valves.
Heating battery. This sets the minimum temperature for the water in the heating
a.
battery (by default, 37°C).
Cooling battery. This sets the maximum temperature for the water in the cooling
b.
battery (by default, 17°C).
Offset. Correction of the room temperature of the different zones of the system in both
cooling and heating mode, with a correction factor between -2.5°C and 2.5°C in steps of
0.5°C. By default, it is set to 0°C.
IAQ Ranges (AirQ Box only) Allows you to define the IAQ measurement ranges (upper and
lower).
Working temperature. Allows you to set the working temperature of the indoor unit
between Thermostat or Return/Probe.
a.
Thermostat: uses as working temperature the temperature measured by the
thermostat.
b.
Return/Probe: uses as working temperature the temperature measured by the remote
probe (AI1).
Third-party thermostat: Uses the temperature measured from KNX or by local API as
c.
the working temperature.
Digital inputs
Presence. Allows control of the status of the device based on the detection of occupancy.
Window. Allows control of the status of the device based on the detection of an open
window.
Eco function. Modifies the selected set-point temperature (+/-2.5°C) for more efficient
management of the thermal demand of its zone.