Télécharger Imprimer la page

Samsung DV25B6900EW Manuel D'utilisation page 19

Masquer les pouces Voir aussi pour DV25B6900EW:

Publicité

Les langues disponibles

Les langues disponibles

Ducting requirements (Not applicable to ventless (heat pump) models)
Weather hood type
No. of 90° elbows
0
1
2
3
NOTE
* Use a 4-inch (10.2 cm) diameter rigid aluminum or galvanized steel duct.
If you integrate the dryer's vent system with an existing exhaust system:
• Make sure the exhaust system meets all applicable local, state, and national regulations.
• Verify you are not using flexible plastic duct.
• Make sure to check for and remove all lint buildup from inside the existing ducts.
• Confirm the duct is not kinked or crushed.
• Make sure the exhaust hood damper opens and closes freely.
Manometer measurements
The static pressure in any exhaust system must not exceed 0.83 inches of water column or be less than 0.
Note that these values are measured with the dryer running with a manometer presented to the exhaust
duct that connects to the dryer. The dryer tumbler must be empty and lint filter clean.
DV6900B_SimpleUX_WEB_Vent_EN.indd 19
Recommended
4" (10.2 cm)
Rigid
80 ft. (24.2 m)
60 ft. (28.3 m)
45 ft. (13.7 m)
35 ft. (10.7 m)
Use only for short-run
installation
2.5" (6.4 cm)
Rigid
60 ft. (28.3 m)
45 ft. (13.7 m)
35 ft. (10.7 m)
25 ft. (7.0 m)
English 
2022/6/7 14:49:26
19

Publicité

loading

Ce manuel est également adapté pour:

Dv25b6900e serieDv25b6900ex/acDv25b6900hw