Télécharger Imprimer la page

Beko BS107CB Mode D'emploi page 18

Publicité

Les langues disponibles

Les langues disponibles

1
Safety instructions
10) When the cylinders have been filled correctly and the process
completed, make sure that the cylinders and the equipment
are removed from site promptly and all isolation valves on the
equipment are closed off.
11) Recovered refrigerant shall not be charged into another
refrigeration system unless it has been cleaned and checked.
10. Labelling
Equipment shall be labelled stating that it has been de-
commissioned and emptied of refrigerant. The label shall be dated
and signed. Ensure that there are labels on the equipment stating
the equipment contains flammable refrigerant.
11. Recovery
When removing refrigerant from a system, either for servicing
or decommissioning, it is recommended good practice that all
refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only
appropriate refrigerant recovery cylinders are employed. Ensure
that the correct number of cylinders for holding the total system
charge is available. All cylinders to be used are designated for
the recovered refrigerant and labelled for that refrigerant
(i.e. special cylinders for the recovery of refrigerant). Cylinders
shall be complete with pressure relief valve and associated
shut-off valves in good working order. Empty recovery cylinders
are evacuated and, if possible, cooled before recovery occurs.
18 / 76 EN
Local air conditioner / User Manuel

Publicité

loading

Ce manuel est également adapté pour:

Bs107cn