Wiring Connections In The Control Box - Mitsubishi Electric CITY MULTI PURY-P72ZKMU-A Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

10-5. Wiring connections in the control box

Connections must be made securely and without tension on the terminals.
- Improperly connected cables may break, overheat, or cause smoke or fire.
10-5-1. Threading power cable through the knockout hole
・Punch out the knockout holes at the bottom of the front panel with a hammer. Use the appropriate knockout hole according to the size of the
power cable, referring to the table below.
・If there are any gaps around the power cable, please be sure to fill these in with a suitable material.
・When putting the power cable through the knockout hole without using a conduit tube, deburr the hole and protect the power cable with protective
tape.
・Use a conduit tube to narrow down the opening if there is a possibility of small animals entering the unit.
・When taking the conduit tube out from the bottom part of the unit, caulk around the tube opening to prevent water infiltration.
WT07828X01
Power cable size (mm
2, 3.5, 5.5
8, 14
21, 26, 33
84, 67, 53
5 4
3 2 1
Cable strap
Power cable
Transmission cable
GB-32
2
)
Knockout hole to be used
Knockout hole 2
Knockout hole 4
Knockout hole 3
Knockout hole 5

Hide quick links:

Publicité

Chapitres

Table des Matières
loading

Table des Matières