VAS 6746B
7.5
Entering the date and time
The date and the time are printed along with the company data on every
service log.
1. In the basic menu, use the cursor keys  or  to select
"Other selections":
2. Press ENTER to confirm.
3. Use the cursor key  to select "Service.".
4. Press ENTER to confirm.
5. Enter the password "8463".
6. Use the keypad and the cursor keys to enter the information.
7. Press ENTER to confirm.
8. Press STOP to access the standby menu.
7.6
Editing default values
The AirConServiceCenter has preset values for the most important
service tasks. The default values appear automatically when you select
the respective menu.
You can alter the following default values if necessary:
Parameter
Pressure increase Test time
Vacuum time min.
Leak Test
PAG Oil
UV Tracer
Filling Qt. g.
Print recovery value ?
1. In the basic menu, use the cursor keys  or  to select
"Other selections":
2. Press ENTER to confirm.
3. Use the cursor key  to select "Service.".
EN
S h o r t s e l e c t i o n
F r e e s e l e c t i o n
O t h e r s e l e c t i o n s
E N T E R - O K S T O P - E X I T ⬍
min.
min.
ml. (additional quantity)
ml.
S h o r t s e l e c t i o n
F r e e s e l e c t i o n
O t h e r s e l e c t i o n s
E N T E R - O K S T O P - E X I T ⬍
Initial start-up
Default value
500
1
20
4
0
7
Yes
83