Installation and Commissioning
SUPPLY VOLTAGE :
For operating voltage reverse polarity protection, a one-way rectifier or
reverse polarity protection diode is integrated in this device variant.
This internal one-way rectifier on AC supply voltage.
The output signal is to be tapped by a measuring instrument. The output
signal is measured her against zero potential (O V) of the input voltage!
When this device is operated on DC supply voltage , the operating voltage
input UB+ is to be used for 15...36 V DC supply and UB – or GND for
ground wire!
When several devices are supplied by one 24 V AC voltage supply, it is to
be ensured that all "positive" operating voltage input terminals (+) of the
field devices are connected with each other and all "negative" operating
voltage input terminals (–) (= reference potential) are connected together
(in-phase connection of field devices). All outputs of field devices must be
referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short-
circuit would be caused by that device. The consequential short-circuit
current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!
Temperature table
Temperature table
MR: –20...+80 °C
MR: –20...+50 °C
°C
U
I
A
A
[V]
[mA]
0.0
4.0
– 20
– 15
0.5
4.8
– 10
1.0
5.6
– 5
1.5
6.4
 0
2.0
7.2
 5
2.5
8.0
10
3.0
8.8
15
3.5
9.6
20
4.0
10.4
25
4.5
11.2
30
5.0
12.0
35
5.5
12.8
40
6.0
13.6
45
6.5
14.4
50
7.0
15.2
55
7.5
16.0
60
8.0
16.8
65
8.5
17.6
70
9.0
18.4
75
9.5
19.2
80
10.0
20.0
Temperature table
MR: 0...+50 °C
°C
U
I
A
A
[V]
[mA]
0.0
4.0
– 20
– 15
0.7
5.1
– 10
1.4
6.3
– 5
2.1
7.4
 0
2.9
8.6
 5
3.6
9.7
10
4.3
10.9
15
5.0
12.0
20
5.7
13.1
25
6.4
14.3
30
7.1
15.4
35
7.9
16.6
40
8.6
17.7
45
9.3
18.9
50
10.0
20.0
Connecting scheme
Power supply
AC 24V~
DC 15-36V = GND
Connecting scheme
Power supply
AC 24V~
DC 15-36V = GND
Temperature table
MR: 0...+100 °C
°C
U
I
°C
A
A
[V]
[mA]
0.0
4.0
 0
 0
 5
1.0
5.6
 5
10
2.0
7.2
10
15
3.0
8.8
15
20
4.0
10.4
20
25
5.0
12.0
25
30
6.0
13.6
30
35
7.0
15.2
35
40
8.0
16.8
40
45
9.0
18.4
45
50
10.0
20.0
50
55
60
65
70
75
80
85
90
95
100
11
Individual operation
Circuitry
0V
V
Circuitry
0V
Humidity table
MR: 0...100 % RH
U
I
%
A
A
[V]
[mA]
RH
0.0
4.0
 0
0.5
4.8
 5
1.0
5.6
10
1.5
6.4
15
2.0
7.2
20
2.5
8.0
25
3.0
8.8
30
3.5
9.6
35
4.0
10.4
40
4.5
11.2
45
5.0
12.0
50
5.5
12.8
55
6.0
13.6
60
6.5
14.4
65
7.0
15.2
70
7.5
16.0
75
8.0
16.8
80
8.5
17.6
85
9.0
18.4
90
9.5
19.2
95
10.0
20.0
100
Parallel operation
Circuitry
U
I
A
A
[V]
[mA]
0.0
4.0
0.5
4.8
1.0
5.6
1.5
6.4
2.0
7.2
2.5
8.0
3.0
8.8
3.5
9.6
4.0
10.4
4.5
11.2
5.0
12.0
5.5
12.8
6.0
13.6
6.5
14.4
7.0
15.2
7.5
16.0
8.0
16.8
8.5
17.6
9.0
18.4
9.5
19.2
10.0
20.0