2.5.2. Teach from IO-Link Master
a) To enable Teach from the IO-Link master first disable the trimmer input:
Select: "0=Disabled" in the Selection of local/remote adjustment parameters 68 (0x44).
b) The individual team commands can be written to index 2.
2.5.2.1. Single point mode procedure
Select the Switching channel to be taught
a) Select: 1=SSC1 or 2=SSC2 in the "Teach-in Select" 58(0x3A) or 255 = All SSC.
b) Change the Hysteresis if requested for SSC1 or SSC2.
"SSC1 configuration" 61(0x3D) "Hysteresis" 3(0x03).
"SSC2 configuration" 62(0x3E) "Hysteresis" 3(0x03).
NB! It is not recommended to change the hysteresis below the values stated in the SSC
parameter list.
1) Single value teach command sequence:
#65 "SP1 Single value teach"
#64 "Teach apply" (optional command)
Command Sequence
1) "SP1 Single value Teach"
2) "Teach Apply"
2) Dynamic teach command sequence
#71 "SP1 dynamic teach start"
#72 "SP1 dynamic teach stop"
#64 "Teach apply" (optional command)
3) Two value teach command sequence
#67 "SP1 two value teach TP1"
#68 "SP1 two value teach TP2"
#64 "Teach apply" (optional command)
Command Sequence
1) "SP1 Two value Teach TP1"
2) "SP1 Two value Teach TP2"
3) "Teach Apply"