ULTRAGRIP STAINLESS STEEL SUPPORT LINERS FOR PE & PVC PIPE SIZES DN40 TO DN400
Fig. 1
Fig. 4
1. Check that the support liner and wedge are suitable for pipe OD and wall thickness.
2. Insert the liner body until the shoulder butts against the pipe end.
3. Insert the wedge until the body touches fully the pipe inside.
4. Mark the wedge 5-10mm from pipe surface. Remove wedge and cut off wedge at the mark.
5. Insert the wedge until face is equal to pipe surface.
SIZES 450MM & ABOVE
Fig. 1
Fig. 4
5-10mm
1. Check that the support liner and wedge assembly are suitable for pipe OD and wall thickness.
(Liner specification details printed on wedge surface)
2. Offer the full assembly to the pipe, and insert until the shoulder tabs butt against the pipe end.
3. Slide each wedge evenly by hand into place, to the same distance, until the liner body makes
contact with the inside pipe surface.
4. Mark both wedges 5-10mm from the pipe surface and cut to this line.
5. Very gently tap the wedges in place, evenly both sides, until the wedges are flush with the
4
pipe surface.
Fig. 2
Fig. 5
Fig. 2
Fig. 5
Fig. 3
Fig. 3