Refrigerant Piping Connection
When connecting refrigerant piping, do not let substances or gases other than the specified
refrigerant enter the unit. The presence of other gases or substances will lower the unit's capacity,
and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and
injury.
Note on Pipe Length
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal
efficiency is tested on units with a pipe length of 5 meters (16.5ft)( In North America, the standard pipe
length is 7.5m (25'). A minimum pipe run of 3 metres is required to minimise vibration & excessive noise.
Refer to the table below for specifications on the maximum length and drop height of piping.
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model
R32 Inverter Split Air
Conditioner
Connection Instructions – Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
care to cut and flare them properly. This will
ensure efficient operation and minimize the
need for future maintenance.
1. Measure the distance between the indoor
and outdoor units.
2. Using a pipe cutter, cut the pipe a little longer
than the measured distance.
3. Make sure that the pipe is cut at a perfect 90°
angle.
Page 29
Capacity (BTU/h)
< 15,000
≥ 15,000 and < 24,000
24,000 and < 36,000
Max. Length (m)
Max. Drop Height (m)
25 (82ft)
30 (98.5ft)
50 (164ft)
90°
Oblique Rough Warped
DO NOT DEFORM PIPE
WHILE CUTTING
Be extra careful not to damage, dent, or
deform the pipe while cutting. This will
drastically reduce the heating efficiency
of the unit.
10 (33ft)
20 (66ft)
25 (82ft)