1/2" Spout
5
Connect the 1/2" ID drain hose to the spout on the
humidifier cabinet using the provided flat spring
clip. Run the drain hose to a suitable drain such as
floor drain, laundry sink or to a condensate pump
(sold separately). Be sure the hose has continuous
slope and is not kinked at any point.
7
Connect the Humidistat (Typical Humidistat & Humidifier Installation Wiring Diagram)
GENERALAIRE
®
GFX4 HUMIDISTAT
YELLOW
WIRES
RED WIRES
24V
SOURCE
INSTALLATION - SUPPLY (ONLY)
Flat Spring Clip
1/2" Drain Hose
AIR PROVING
SWITCH (FIELD
SUPPLIED)
GENERALAIRE
4400A FAN ASSIST
®
EVAPORATIVE HUMIDIFIER
GFX4 Digital
Automatic Control
6
Test the Operation of the Unit
1.
Turn on the water supply.
2.
Turn the humidistat RH% to 60% or higher.
3.
Turn the furnace on; heat cycle. Make sure the furnace
blower motor is on.
4.
Once the solenoid valve is energized the valve should open.
5.
Check flow of water through distributor trough and
evaporator pad.
6.
Check fan operation (ON).
7.
Reduce RH% to desired setting after test completion.
®
®
120V
6" POWER SUPPLY
CORD
®
®
GFX4 Digital
Automatic Control
®
®
3