Fresh Indoor Air Quality
INSTALLER: PLEASE FILL OUT AND MAIL WARRANTY CARD AFTER INSTALLATION
IS COMPLETE. LEAVE INSTALLATION INSTRUCTIONS WITH HOME OWNER.
PRECAUTION: The installer should be an experienced service technician. Disconnect electrical power before
beginning installation. Do not install where temperatures fall below 32 degrees F or where plenum temperatures
exceed 150 degrees F. For maximum evaporative capacity, install this humidifier on the warm air supply plenum.
ADDITIONAL MATERIALS THAT MAY BE NECESSARY:
1. 1/4" diameter plastic supply tubing or 1/4" copper supply tubing for hot water applications
2.
current sensing relay (G.F. Model #GA50 suggested)
1
14-1/8"
Select location on vertical surface of warm air plenum of a forced air
handling system for mounting humidifier that allows for service and
maintenance. Do not install humidifier where the blanked off ends of a
cooling coil will restrict air flow to the humidifier. Cut out a square section
12-1/8" tall by 14-1/8" wide as shown.
2
Open cover and remove evaporator pad assembly. Humidifier chassis is
self retaining, slide top side in first then slide chassis down. Level chassis
and install eight screws.
3
Mount the self tapping saddle valve on either a cold or a hot water pipe.
A side or top mount is best to avoid clogging from pipe sediment.
Connect 1/4" O.D. tubing to the saddle valve. Copper tubing requires a
brass compression nut and brass sleeve. Plastic tubing requires a brass
insert inside the tubing in addition to a plastic ferrule and brass nut.
NOTE: DO NOT USE PLASTIC TUBING ON HOT WATER OR IN
CONTACT WITH ANY HOT PLENUM SURFACE OR DUCT.
INSTALLATION OF THIS SADDLE VALVE MUST MEET OR EXCEED
LOCAL CODES AND ORDINANCES.
FORM NO. 1000-16 REV. E
R
12-1/8"
1
2
COPPER
TUBING
PLASTIC
TUBING
3. junction box, 115 V. grounding outlet, cover and wire
4. 1/2" I.D. drain hose
5.
#8 self piercing sheet metal screws
4
Connect 1/4" water supply tube to inlet of solenoid.Connect drain hose
to 1/2" spout on humidifier cabinet using hose clamp if necessary. Run
1/2" hose to suitable drain such as floor drain, sewer or laundry sink. Be
sure hose has continuous slope and is not kinked at any point.
GCV3412 CODE VALVE INSTALLATION INSTRUCTIONS
Copper Pipe
1. Turn off water supply.
2. Clean pipe, fittings and valve with sandpaper or wire brush.
3. Apply a thin layer of flux to all surfaces to be soldered.
4. Assemble valve to pipe and/or fittings.
5. Cooling the valve by wrapping a wetted rag around the valve is
optional.
6. Heat the joints with a torch. Apply solder to each joint. Continue to
apply heat sufficient to keep solder liquid.
7. After solder has filled entire joint area, remove heat and allow joint
to cool. Do not move or disturb.
8. Slide compression nut over 1/4" copper tube followed by
compression sleeve.
9. Insert tube into valve fully and tighten nut.
10. Turn on water supply and check for leaks.
*CODE VALVE IS INCLUDED WITH AUTOMATIC MODELS ONLY
3/4" TEE
1000 SERIES
FLOW THROUGH
POWER HUMIDIFIER
FOR INSTALLATION ON A VERTICAL
SURFACE OF THE WARM AIR PLENUM
OF ANY FORCED AIR FURNACE
1/2" TEE

Publicité

Table des Matières
loading

Sommaire des Matières pour GeneralAire Elite Serie

  • Page 1 1000 SERIES Fresh Indoor Air Quality FLOW THROUGH INSTALLER: PLEASE FILL OUT AND MAIL WARRANTY CARD AFTER INSTALLATION POWER HUMIDIFIER IS COMPLETE. LEAVE INSTALLATION INSTRUCTIONS WITH HOME OWNER. FOR INSTALLATION ON A VERTICAL PRECAUTION: The installer should be an experienced service technician. Disconnect electrical power before SURFACE OF THE WARM AIR PLENUM beginning installation.
  • Page 2 GFX3 ELECTRONIC HUMIDISTAT MHX3 MANUAL HUMIDISTAT OUTDOOR TEMP. SENSOR (NOT USED IN MANUAL MODE) HUMIDIFIER CONTROL LEADS (YELLOW WIRES) 24V OUTPUT FROM HUMIDIFIER (RED WIRES) OR DUCT MOUNT PLATE STANDARD FOR USA WALL MOUNT PLATE 727-58 24 V. TRANSFORMER WITH CONSTANT POWER OPTIONAL ACCESSORY FOR STANDARD FOR CANADA OR 24 VAC POWER SUPPLY WITH CONSTANT POWER...
  • Page 3: Care And Maintenance

    PARTS LIST FOR HUMIDIFIER 900-9 NOZZLE 900-40 PAD RAIL 900-10 SPOUT GA19 EVAPORATOR PAD 900-15 DISTRIBUTOR TROUGH GA4247 FAN BLADE GA4237 MOTOR 900-71 NAMEPLATE 1000-11 HARNESS - BOARD GA4238 RELAY ASS'Y 900-14 DRAIN PAN 1137-31 POWER SUPPLY CORD GA4231 ORIFICE - YELLOW P-190 COMPRESSION SLEEVE (PLASTIC)/P102 COPMRESSION SLEEVE (BRASS) P-101 COMPRESSION NUT GA4235 DISTRIBUTOR TUBE...
  • Page 4: How The Humidifier Works

    1. Reduce the setting on the humidistat. Refer to CARE AND MAINTENANCE section of this manual to estimate a condensation on windows humidity setting for the home based on outside temperature. * 1. Replacement parts can purchased through your authorized GeneralAire contractor or visit www.GeneralAire.com Where can I purchase for more information.
  • Page 5 ELITE 1000 HUMIDIFIER SPECIFICATIONS Expected Humidity Performance Coverage in Square Feet Based on Construction Type Average (0.50 AC/H) Tight (0.30 AC/H) Model No. Loose (0.75 AC/H) 2000 sq. ft. Elite 570 800 sq. ft. 1200 sq. ft. 1650 sq. ft. 2800 sq.
  • Page 6 WARRANTY REGISTRATION You may register online at www.GeneralAire.com or mail form below Product Information: Serial Number: _____________________________________________________________ Model: ____________________________________________________________________ Install Date: Month _______________ Day ______________ Year _____________ Fresh Indoor Air Quality Owner Information: Name: _____________________________________________________________________ Address: ___________________________________________________________________ Mail Form To:...
  • Page 7 SÉRIE 1000 Qualité de l’air frais intérieur HUMIDIFICATEUR À INSTALLATEUR : VEUILLEZ REMPLIR ET POSTER LA CARTE DE GARANTIE UNE ALIMENTATION CONTINUE FOIS L’INSTALLATION TERMINÉE. LAISSER LES DIRECTIVES POUR UNE INSTALLATION SUR LA D’INSTALLATION AU PROPRIÉTAIRE DE LA MAISON. SURFACE VERTICALE DU PLÉNUM PRÉCAUTION : L’installateur doit être un technicien qualifié...
  • Page 8 HUMIDISTAT ÉLECTRONIQUE GFX3 HUMIDISTAT MANUEL MHX3 DÉTECTEUR DE TEMPÉRATURE EXTÉRIEURE (NON UTILISÉ EN MODE MANUEL) FILS DE COMMANDE DE L’HUMIDIFICATEUR (FILS JAUNES) SORTIE DE 24 V DE L’HUMIDIFICATEUR (FILS ROUGES) OU PLAQUE DE MONTAGE SUR CONDUIT STANDARD AUX PLAQUE DE MONTAGE É.-U., ACCESSOIRE EN OPTION 727-58 TRANSFORMATEUR DE 24 V AVEC ALIMENTATION CONSTANTE MURAL STANDARD AU...
  • Page 9: Liste Des Pièces Pour L'humidificateur

    LISTE DES PIÈCES POUR L’HUMIDIFICATEUR 900-9 GICLEUR 900-40 RAIL DU TAMPON 900-10 BUSE GA19 TAMPON D’ÉVAPORATION 900-15 GOULOTTE DU DISTRIBUTEUR GA4247 PALE DE VENTILATEUR GA4237 MOTEUR 900-71 PLAQUE SIGNALÉTIQUE 1000-11 FAISCEAU - CARTE DE CIRCUITS IMPRIMÉS 900-14 BAC DE RÉCUPÉRATION GA4238 ENSEMBLE DU RELAIS 1137-31 CORDON D’ALIMENTATION GA4231 ORIFICE - JAUNE...
  • Page 10: Dépannage

    5. Véri er le câblage de l’humidi cateur et de l’humidistat. 6. Contacter un installateur GeneralAire autorisé pour qu’il véri e la tension d’entrée et de sortie de la carte de circuits imprimés du relais et la remplace si nécessaire.
  • Page 11: Caractéristiques De L'humidificateur Elite 1000

    CARACTÉRISTIQUES DE L’HUMIDIFICATEUR ELITE 1000 Performance d’humidité prévue selon la superficie en mètres carrés/pieds carrés et le type de construction Moyen (0,50 CAH) Élevé (0,30 CAH) Nº de modèle Faible (0,75 CAH) 186 m /2000 pi Elite 570 74 m /800 pi 111 m /1200 pi...
  • Page 12 ENREGISTREMENT DE LA GARANTIE Le produit peut être enregistré en ligne au www.GeneralAire.com ou par la poste en envoyant le formulaire ci-dessous Renseignements sur le produit : Numéro de série : ____________________________________________________________ Modèle : ___________________________________________________________________ Date d’installation : Mois _______________ Jour ______________ Année ____________ Qualité...