MENU
Enables or disables automatic closing
TCA
On: automatic closing enabled
Off: automatic closing disabled
Enables or disables condominium function.
On: condominium function enabled. The step-by-step impulse or transmitter
IbL
impulse has no effect during the opening phase.
Off: condominium function disabled.
Enables or disables rapid closing
On: rapid closure is enabled. With open gate, or in the opening phase, the
SCL
activation of the photocell causes the automatic closure 3sec after the total
opening of the gate. It is activated only with TCA:ON
Off: rapid closing disabled.
Enables or disables slowing.
On: Slowing active.
Sld
Off: Slowing excluded.
If the logics NOLS=ON, braking cannot be excluded.
Selects the operating mode of the "Step by step button" and of the
transmitter.
PP
On: Operation: OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >
Enables or disables pre-blinking.
PRE
On: Pre-blinking enabled. Blinking is activated 3s before the motor starts.
Off: Pre-blinking disabled.
The lock function in the opening phase is enabled or disabled.
On: Enabled lock function. Only with logics NOLS=OFF.
After activation of the opening limit switches, the control unit delays stop by
Blco
approximately 0.5sec, so as to allow a better stop of the gate leaf against the
stoppers.
Off: Disabled lock function.
The lock function in the closing phase is enabled or disabled.
On: Enabled lock function. Only with logics NOLS=OFF.
After activation of the closing limit switches, the control unit delays stop by
Blcc
approximately 0.5sec, so as to allow a better stop of the gate leaf against the
stoppers.
Off: Disabled lock function.
Selects the mode of the OPEN input
On: OPEN input with CLOCK function.
CLOC
To be used for connection to a timer for timed opening/closing. (Contact
CLOSED- gate open, Contact open, normal operation).
Off: OPEN input with OPEN function
Enables or disables Man present function.
On: Man Present operation.
During the entire operation, the OPEN/CLOSE push-buttons must be kept
htr
pressed. When the STOP input opens, the motor stops. All safety inputs are
disabled.
Off: Automatic operation.
Selects the type of electric lock used.
On: Magnetic electric lock, normally fed at 12Vac/O,5A max.
Before each opening manoeuvre the power supply is interrupted for the time set
mloc
by the parameter TLOC.
Off: Electric lock with latch, normally not fed.
Before each opening manoeuvre power is fed at 12Vac for the time set by the
parameter TLOC.
Select the 1/2 motors operating mode:
1mot
On: Only motor 1 operating.
Off: Both motors operating.
14
FUNCTION
ON-OFF-
MEMO
(Default)
(ON)
(OFF)
(OFF)
(ON)
(OFF)
(OFF)
(OFF)
(ON)
(OFF)
(OFF)
(OFF)
(OFF)