DEFINITION FOR ILLUMINATED LCD INDICATORS
1.
Input voltage meter: This meter measures the AC voltage from
the wall outlet. The INPUT voltage readout is used to identify the
input voltage information. This can be used as a diagnostic tool to
identify poor-quality input power. Units are listed in V (Volts).
When the UPS connect to any equipment, the AVR can provide a
stable
220/230/240V power output. In the event of a complete
loss of power, severe brownout, or over voltage, the UPS relies on
its internal battery to back up to supply a consistent 220/230/240V
output.
2.
Output voltage meter: The Output Voltage screen measures, in
real time, the AC voltage that the UPS is providing to your
connected equipment via the UPS outlets. Units are listed in V
(Volts).
3.
Estimate run time: The Estimated Runtime Screen displays how
many minutes of runtime can be expected of the UPS if it were to
experience a power outage. When runtime becomes shorted, the
battery capacity will decrease; (battery capacity bar indicator will be
falling.) Note: The number displayed may be less than actual
runtimes for low loads.
4.
Normal icon: This icon illuminates when the UPS is working under normal conditions.
5.
Battery icon: When there is a severe brownout or blackout, this icon will appear followed by an alarm,
(two short beeps), indicating that the UPS is now working using its internal batteries. Once the batteries
are run out of power, (over a period of time), a constant alarm will sound. If this happens and main power
has not been restored, it is recommended that you save your files and turn off your equipment manually
as soon as possible.
6.
Automatic Voltage Regulation (AVR) icon: This icon will appear when the unit is automatically
regulating low or high AC input line voltage conditions, without resulting to the use of battery power.
7.
Silent mode icon: This icon appearing indicates that the buzzer will not be beeping while in battery
operating mode. During Silent mode, the unit's alarm does not sound until the Battery Capacity falls to <
20%.
8.
Over load icon: This icon will appear followed by an alarm, indicating that an overload condition has
been reached. To recover from the overload condition, start unplugging your equipment from the UPS
outlets until the icon disappears and the alarm stops.
9.
Fault icon: When activated indicates a system fault error. Please refer to the troubleshooting table for
possible causes and solutions.
10. BATT. CAPACITY: BATT. CAPACITY is shown as a bar chart; each segment indicates approximately a
20% of battery capacity.
11. LOAD CAPACITY: Load CAPACITY is shown as a bar chart; each segment indicates approximately a
20% of load capacity.
7
□
11
□
10
□
4
□
1
The LCD displays detailed information on
the UPS status and current power
conditions to alert you to potential power
problems
equipment.
information is based on that you should
turn on the UPS.
Copyright © 2009 CyberPower Systems, Inc.
□
5
□
6
□
7
□
8
□
9
□
□
2
3
before
the
affect
your
Note!
All
related
UPS