AKO 15645 Guide Rapide page 28

Masquer les pouces Voir aussi pour 15645:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Level 1.- Defrost Control
d0 Defrost frequency (Time between two starts)
d1 Maximum defrost duration (0=defrost deactivated)
Type of message during defrost:
d2
0=Current temperature; 1=Temperature at start of defrost; 2=Display dEF message
Maximum duration of message
d3
(Time added at the end of the defrost process)
d4 Defrost end temperature (probe 2) (If P4 ¹ 1)
Defrost on equipment start-up:
d5
0=NO, First defrost as per d0
1=YES, First defrost as per d6
d6 Defrost start delay on equipment start-up
Defrost type:
d7
Calculated time between defrost period:
d8
0=Total actual time; 1 =Sum of times the compressor is on
Drip time at end of defrost
d9
(compressor and fans off) (if P4 ¹ 1)
EP Exit Level 1
Level 1.- Fan control
Fan shut-down temperature as per probe 2
F0
(if P4 ¹ 1)
F1 Probe 2 differential (If P4 ¹ 1)
F2 Stop fans when stopping compressor 0=No, 1=Yes
Fan status during defrost:
F3
0=Off; 1=On
Starting delay after defrost (if F3=0)
F4
Will only operate if it is higher than d9
EP Exit Level 1
Description
0=Resistors,
2=Fan / air / Compressor off
Description
1=Inverted cycle,
28
Units
Min
Def
Max.
(h.)
0
6
96
(min.)
0
15
255
0
2
(min.)
0
5
255
(ºC/ºF)
-50
8.0
99,0
0
0
(min.)
0
0
255
0
0
0
0
(min.)
0
1
255
Units
Min
Def
Max.
(ºC/ºF)
-50
45
99,0
(ºC/ºF)
0,1
2,0
20,0
0
1
0
0
(min.)
0
3
99
2
1
2
1
1
1

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

15646156481562615627

Table des Matières