"Service completed" displays the amount of service work performed
using the air conditioning service unit since the last reset (see date).
9.4.1
Leak test
After changing the filter, perform a leak test with an approved testing
device.
9.5
Calibrating the pressure transducer
I
NOTE
The pressure transducer has to be correctly calibrated in order to make
accurate pressure measurements.
Calibration is required:
 Every four weeks
 If the AirConServiceCenter has been subjected to heavy shaking
 Every time the vacuum pump oil is changed
 If the display shows implausible pressure readings
1. In the basic menu, use the cursor keys  or  to select "Other
selections":
2. Depressurise the unit (as described in chapter "Changing the dryer
filter" on page 102).
3. Press ENTER to confirm.
4. Use the cursor keys  or  to select "Service":
5. Press ENTER to confirm.
6. Enter the password "2224".
7. Confirm "Pressure transducer" by pressing ENTER.
EN
Service completed:
Number
STOP-EXIT
Short selection
Free selection
Other selections
ENTER-OK
Int. vessel filling
Flushing
Reset scales.
Service.
Service tasks
08/03/15
4
105