ASC5000, ASC5000G
"Service completed" displays the amount of service work performed
using the air conditioning service unit since the last reset (see date).
9.4.1
Leak test
After changing the filter, perform a leak test with an approved testing
device.
9.5
Calibrating the pressure transducer
I
NOTE
The pressure transducer has to be correctly calibrated in order to make
accurate pressure measurements.
Calibration is required:
Every four weeks
If the AirConServiceCenter has been subjected to heavy shaking
Every time the vacuum pump oil is changed
If the display shows implausible pressure readings
1. In the basic menu, use the cursor keys or to select "Other
selections":
2. Depressurise the unit (as described in chapter "Changing the dryer
filter" on page 102).
3. Press ENTER to confirm.
4. Use the cursor keys or to select "Service":
5. Press ENTER to confirm.
6. Enter the password "2224".
7. Confirm "Pressure transducer" by pressing ENTER.
EN
Service completed:
Number
STOP-EXIT
Short selection
Free selection
Other selections
ENTER-OK
Int. vessel filling
Flushing
Reset scales.
Service.
Service tasks
08/03/15
4
105