TROUBLESHOOTING
PROBLEM
On giving a command with the remote control or
with the key-switch, the gate doesn't open or the
motor doesn't start
On giving a command with the remote control, the
gate doesn't open but works with the key com-
mand
The gate starts, but stops immediately
One wing opens and the other closes
N.B. - If the problem persists, contact your Retailer or the nearest Service Centre
EA32
PROBABLE CAUSE
230 volt mains voltage absent
Emergency STOP present
Fuse blown
Power cable of motor or motors not connected or
faulty.
The photocell is not functioning or the beam is in-
terrupted
The remote control has not been memorised or the
battery is flat
The force of the motor or motors is insufficient
The connection is not correct
12/32
SOLUTION
Check master switch
Check for any STOP selectors or commands.
If not used, check jumper on STOP contact input
on the control board
Replace with one of same value.
Connect the cable to appropriate terminal or re-
place.
Check the connection, remove any obstacle across
the beam
Carry out the remote control learning procedure on
the radio receiver or replace the battery with a new
one.
Modify the value with the FORCE trimmer on the
control unit
Invert the connection of the cable of the motor
which rotates in the wrong sense.