Service tasks
5. Press ENTER to confirm.
6. Enter the password "2224".
7. Confirm "Pressure transducer" by pressing ENTER.
8. Then follow the instructions in the display.
– Unscrew the service couplings (15) and (16) from the service
hoses (13) and (14).
– Use the keypad (8) to enter the current local atmospheric pressure
and press ENTER to confirm.
I
NOTE
You can look up the current atmospheric pressure for your region on the
Internet, for example at http://www.meteo24.de/wetter/ under "air pres-
sure".
9. When calibration has been completed, press ENTER to exit the
menu.
10. Press STOP twice to access the standby menu.
11. Screw the service couplings (15) and (16) hand-tight onto the service
hoses (13) and (14), taking care not to mix up the red and blue mark-
ings on the couplings and hoses.
114
ASC5000RPA/ASC5500RPA
EN