3-12. Output Peak Power
Operating conditions for peak power/current models:
(a)
Reduce peak current according to output derating curve for higher ambient temperature
(see section 5.1)
(b)
Output might shut down when the rated current or the continuous peak output time ()
exceeded rated value specified. Power supply may shut down and operate in hiccup or
constant current limiting mode.
Input voltage :
Continuous peak out time () :
Peak output current (Ip) :
Duty: not more than 35%

Duty = ---- x 100 (%)
T

2
Ip
x ----
T
Applicable model for Peak Output Power:
Model
LS200-24
LS200-36
115 ~ 230 VAC +/- 20% (50/60 Hz)
< 10s
Within the rated peak output current
< Irms max
Irms max.
6.15 A