6.4.1.2
Cleaning the heat exchanger
ATTENTION
Damage to components
Damage to the heat exchanger fins due to incorrect cleaning.
Clean the heat exchanger fins with a soft brush, compressed air or a vacuum cleaner with a brush attachment.
NOTE
The time intervals for cleaning depend strongly on the contamination of the ambient air.
Fig. 28: Cleaning the heat exchanger
Operating Manual | Attachment and Installation Cooling Units | Multi Controller (MC) – 400 / 460 V, 3~ | 086100124
Prerequisites
DANGER – Danger to life due to electric shock. Make sure that the
unit is voltage-free.
The unit cover is removed, see chapter "Removing/assembling the
unit cover", Page 60.
Required tools and materials
Soft brush
Vacuum cleaner with brush attachment or compressed air cleaner
Fin comb
Procedure
1.
Clean heat exchanger fins (1) and condenser fan (2) with a soft
brush, with compressed air or with a vacuum cleaner with brush
attachment.
CAUTION – risk of injury. Do not touch the sharp heat
exchanger fins.
CAUTION – dust development when cleaning with compressed
air. Wear eye, mouth and nose protection when cleaning with
compressed air.
2.
Check heat exchanger for bent fins; straighten fins with fin comb.
3.
Refit the unit cover.
4.
Check that the cooling unit works properly and safely after cleaning.
The heat exchanger is cleaned.
G00026-01
62/76

Publicité

loading

Ce manuel est également adapté pour:

Dti 6401Dts serie