3.2 Product description

The airflow recorded by the measuring probe
is compared with the setpoint defined in the
control unit. If the setpoint is reached or
exceeded, the integrated relay is activated.
There is no problem switching ventilation
components. The time steps t1 to t4 that are
stored in the control unit guarantee the
vibration-free start up of a fan, for example.
Product features
● With adjustable switching point.
Adjustment range: 0.1 to 20 m/s
● Installation of control unit on a 35 mm profile
rail.
● LED function display for relay outputs and
nominal voltages.
● Relay output for external fault display.
● Working and closed circuit function
selection switch.
● With potential-free output via a change-
over contact.
Time steps T1 to T4
t1 Switch-on time after applying mains
power/power supply (approx. 100 ms).
R1 contacts 3 and 4 closed.
t2 Time for start-up bridging (approx. 50 s).
Relay R1 is activated for this time,
irrespective of the actual air flow value.
R1 contacts 4 and 5 closed, yellow LED [2]
flashes. Following this, the air flow monitor
works in normal mode, in accordance with
the defined setpoint.
t3 Minimum time difference for the restart of
t2 (approx. 300 ms).
t4 Measuring sensor reaction time (approx. 2 s).
3. Product Information │ uk

3.3 Intended use

● Air flow monitor for monitoring the
minimum volumetric flows in ventilation
systems.
● Operation is only permitted:
● with correctly assembled measuring
probe.
● with the control unit mounted in the
control cabinet on a 35 mm profile rail.
● Screen cables are prescribed if the sensor
cable is installed in cable channels.

3.4 Predictable misuses

Maico is not liable for damages caused
by use contrary to the intended purpose.
Under no circumstances should the unit
be used:
● close to flammable materials, liquids
or gases.
● for conveying chemicals, aggressive
gases or vapours.
● in explosive atmospheres.
● under mechanical load.
4. Environmental conditions and
operating limits
Ambient temperature
Control unit
Measuring probe
Permitted humidity
in accordance with
EN 60721-2-3
- 20 ... + 60 °C
- 30 ... + 80 °C
Class 3K3
(15 ... 85%)
without
condensation
9