Code for voltage and No. of poles
acc. to UL
Voltage
Colour face
2-pole + PE
(PE)
125V 60Hz
yellow
250V 60Hz
blue
480V 60Hz
red
3-pole + PE
600V 60Hz
black
480V 60Hz
red
250V 40Hz
blue
125/250V 60Hz
orange 12 h
3-pole + N + PE
600V 60Hz
black
277V 60Hz
red
120/208V 60Hz
blue
Dimensions in mm
X = fixing dimensions
Wall socket,
4- and 5-pole
Plug, 4- and 5-pole
2 2 2 2 2
Cooper Crouse-Hinds GmbH
Annex to operating instructions
Plug and socket system 60A, GHG 514
1 1 1 1 1
T T T T T echnical data
echnical data
echnical data
echnical data
echnical data
1.1
1.1
Plug and socket GHG 514
Plug and socket GHG 514
1.1
1.1
1.1
Plug and socket GHG 514
Plug and socket GHG 514
Plug and socket GHG 514
Explosion category:
for USL
for CNL
Certifications and Compliances:
for CNL
Rated voltage:
Rated current:
Back-up fuse:
without thermal protection
Clock
with thermal protection
Switching capacity:
Perm. ambient temperature:
4 h
Special versions permit deviating temperatures.
6 h
Perm. storage temperature in original packing:
7 h
Protection category acc. to IEC 60529
with closed and secured hinged cover as well
as combinations properly plugged together
5 h
Insulation class acc. to IEC 61140:
7 h
Cable entry:
9 h
Wall socket
plug / Coupler
Supply terminal:
Wall socket
5 h
7 h
Plug
9 h
Test torques:
Cover screws
Terminals, plug
Terminals, wall socket
Self-cutting screws size 4
Self-cutting screws size 5
Self-cutting screws size 8
Weight:
wall socket
plug
wall socket
plug
Auxiliary contact:
Rated voltage:
Rated current:
Switching capacity:
Contact arrangement
GHG 514, 4-pole 50/60Hz
w/o auxiliary contact
contact
AEx de II C T6
Ex de II C T6
Class I, Zone 1
Class I, Division 2 -
Class II, Division 1 -
up to 600 V, 60 Hz
max. 60 A
max. 60 A
max. 80A gL
690V / 80A
-20° C to + 40° C (catalogue version)
-55° C to + 80° C
IP 66 (catalogue version)
I - is complied with by the devices
(catalogue version)
2 x M40, (1 x hub M40/1/4" NPT, 1 x blanking plug)
Ø 26 - 34 mm
Cross section
2 x AWG 11 - 4
(with cable lugs 1 x AWG 2)
1 x AWG 11 - 5
(with cable lugs 1 x AWG 4)
2.5 Nm
2.4 Nm
3.5 Nm
2.0 Nm
3.0 Nm
3.5 Nm
(catalogue version)
4-pole
GHG 514 44
approx. 8.10 kg
4-pole
GHG 514 74
approx. 0.75 kg
5-pole
GHG 514 45
approx. 8.15 kg
5-pole
GHG 514 75
approx. 0.80 kg
690V VAC
20A
AC 15
DC 13
with auxiliary
w/o auxiliary contact
Groups A, B, C and D
Groups F and G
Stripped wire length
19 mm
12 mm
400V / 6A
24V / 2A
GHG 514, 5-pole 50/60Hz
with auxiliary
contact