WARNING/RESTRICTIONS:
RIGGING/HOIST CONTROL OR SECURITY EQUIPMENT CONTROL WITH DGT6(S)RL / DP6(S)RL
IS TOTALLY FORBIDDEN.
COMPULSORY SETTINGS DGT6(S)RL / DP6(S)RL (Factory Default Settings):
- Dimming Curve « RS » for all 6 channels
- Smoothing = OFF
- Soft start = OFF
- Limit = FF (100%)
After a general reset or a Zero Power Ram replacement on the CPU, those settings have to be set.
It is recommended not to send any RDM command to the DGT6(S)RL / DP6(S)RL.
Maximum Load per channel:
Maximum Load per channel:
- The maximum load per channel according to the power factor of the load are indicated on
DGT6(S)RL / DP6(S)RL and also depends on the chosen technology.
- Loads having a power factor < 0.40 cannot be connected to DGT6(S)RL / DP6(S)RL.
- The maximum switch speed for an ON or OFF cycle of 2 seconds.
Strobe function is not allowed.
Possible causes for the reduction of the Relay switching life expectancy :
- Switching speed
- Reactive Power of the load (Power factor)
- Temporary Overload