Télécharger Imprimer la page

Lamborghini Caloreclima EM 12-E Notice D'installation Et D'entretien page 39

Bruleurs a gaz a une flamme pour chaudieres normales/pressurisees
Masquer les pouces Voir aussi pour EM 12-E:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

EM 18/2-E
Legend
1 Control box
2 7 Poles connector
4 Valve gas
5 Anti-interference filter
6 Ignition transformer
7 Fuse
8 Main switch
9 Gear motor for air shutter opening
10 Remote lock-out warning light
WARNING:
- Do not invert the neutral with the phase.
- Make the connection to an effi cient earthing system.
- The electrical power line to the burner must be fi tted with an omnipolar switch with an ope-
ning of at least 3 mm between the contacts.
- The earth connection to the terminal board of the burner must be made with a cable at least
20 mm longer than the phase and neutral cables.
- Must be workmanlike performed and comply with the regulations in force.
NOTE: Always make sure that no more than two wires are connected to each terminal.
11 Temperature boiler thermostat
13 Burner motor
14 Air pressure switch
15 Min. gas pressure switch
16 Control electrode
17 Room thermostat
18 Boiler thermostat
UK