Télécharger Imprimer la page

Tripp-Lite SmartOnline SV Serie Manuel De L'utilisateur page 25

Publicité

Les langues disponibles

Les langues disponibles

9. Control Panel
Time
Change Password
Audible Alarm
Factory Reset
EEPROM Reset
EPO Function
Save Setting
9.3.6.2 System
The SETUP – SYSTEM screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to table
9.4 for details.
SYSTEM
Battery Mode Delay Time*
System Shutdown Time*
System Restore Time*
SmartOnline SV-Series UPS Operating Mode
Standby
Bypass
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Set output voltage: 120/127V (Default: 120V)
Output Voltage
Voltage – Upper limit: +10/15%; Lower limit: -10/20% (Default: +15/-20%)
Bypass Setting
Frequency – Upper limit: +1/2/4Hz; Lower limit: -1/2/4Hz (Default: +/- 4 Hz)
Set "Disable" or "Enable" (Default: Disabled)
Converter Mode
Set "Disable" or "Enable" (Default: Disabled)
ECO Mode
Set "Disable" or "Enable" (Default: Enabled)
Bypass Mode
Set "Disable" or "Enable" (Default: Enabled)
Auto Restart
Set "Disable" or "Enable" (Default: Disabled)
Cold Start
Refer to 7.3 Cold Start for more information
Set system shutdown delay time in battery mode (0-9990 sec.)
Set system shutdown time 0.2 – 99 min. (Default: 0.2 min.)
Set system restore time 0-9999 min. (Default: 001)
Total Power - Quantity of Power Modules installed
Redundancy*
Redundancy - Quantity of Power Modules to be redundant
Set "Disable" or "Enable" (Default: Disabled)
Charger Test
When this feature is enabled and the battery breaker of the UPS system is on, LCD can
display the charger voltage
Line
Battery
Battery Test
Y
Y
Y
Y
Y
Y
Table 9.3
25
Fault
Converter
Y
Y
Y
Y
Y
Y
ECO
Y
Y
Y
Y
Y
Y

Publicité

loading

Ce manuel est également adapté pour:

Smartonline sv20pm