THERMOSTAT KIOUR - FR (-2 +8⁰C-FREEZERS)
Operating instructions
Push [ ] to enter the parameters menu. The first parameter (SPo) shows up. Scroll the parameter list by pressing key [ ] or [ ].
1)
Press [set] to display a parameter value and modify it by pressing the arrows. Press [ ] to save the new value.
2)
To exit the parameter menu press [ ].
3)
4)
On/off switch: Press
5)
T2 ():
6)
Reset ():
7)
Df (set):
8)
Network connection: The thermostat can be connected on a network (RS485 Modbus protocol) through interface.
Alarm messages:
ALo:
Low temperature alarm
LF1:
Room sensor failure
Dor:
Open door alarm (when a door remains more than 2 minutes opened)
Code
1
SPo
2
ALo
3
AHI
4
Dr1
5
Cod
6
DiF
7
dd2
8
dP3
9
dY4
10
dE5
11
Dt6
12
AF1
13
At2
14
Fo1
15
Ft2
16
Fd3
17
Co1
18
Cp2
19
CF3
Compressor control for T1 fault
20
CF4
Compressor off time for T1 fault
21
SE1
22
SE2
23
SEr
24
LSP
25
HSP
Alter temperature measurement
unit (changing the unit will not
affect setpoint and limit values –
these values must be changed
manually)
26
CF
27
Br
Baud Rate (9600)
28
tr
Response time on network (mSec)
29
Ad
for 3 seconds to switch the device off.
Press to see the evaporator temperature.
In case of alarm situation, press to reactivate.
Press [set] for 4 seconds to start a manual defrost cycle.
AHi:
LF2:
Description
Temperature setpoint
Low alarm threshold
High alarm threshold
Defrost repetition time
Access code
Thermostat delay
Defrost time out
Dripping time
Defrost display control
Defrost end temperature
Defrost type
Alarm setting
Temperature alarm delay
Fan restart temperature
Evaporator fan control
Ventilation in defrost
Compressor minimum on time
Compressor minimum off time
Probe T1 offset
Probe T2 offset
-
Minimum temperature setting
Maximum temperature setting
Network address
BRIEF INSTRUCTIONS MANUAL
High temperature alarm
Evaporator sensor failure
PARAMETER SETTINGS
Minimum - Maximum Limits
LSP . . .HSP
0
-45 . . . 20
C
0
0 . . . 60
C
1 . . . 100 h
0
1 . . . 20
C
0 . . . 100 min
0 . . . 15 min
-1 . . . 40 min
(-1: Displays Dfr while
t>Spo+dif)
0
1 . . . 70
C
0= ELE / 1=GAS
0=Auto, 1=Manual
-1 . . . 120 min (-1: alarm
disabled)
0
-50 . . . 50
C
-1: Continuous function
0: Parallel with compressor
0-15 min: time fan stops after
compressor
0: off
1: Starts when t2<Fo1
2: on
0 . . . 15 min
0 . . . 15 min
-1: compressor off
0: compressor on
1-150 min: compressor on time
1-150 min
0
-20 . . . 20
C
0
-20 . . . 20
C
0
-50 . . . 100
C
0
-50 . . . 100
C
0 = 0°C, 1 = 0°F
1.......10
5 . . .20 msec
0 . . .255
9
Settings
Settings (Freezers)
(-2 +8⁰C)
-18
-25
0
6
22
22
2
30
15
2
-1
30
15
0
0
30
15
-2
10
-1
0
2
2
3
3
0
-21
-10
0
1
20
20
2
-2
-5
8
3
3
2
-1
0
0
-1
0
2
2
3
3
0
-2
8
0
1
2