ENG
2
Safety
2.1
Intended use
The Pfannenberg add-on and built-in cooling units of the DTS and DTI series are stationary cooling units for heat dissipation
from switch cabinets. They are available in two versions:
•
The DTI cooling units are installed partly sunken into the side or door.
•
The DTS cooling units are mounted on the side or door.
WARNING
Risk of injury due to impermissible use of the units.
Improper use of units can lead to serious accidents.
•
Only use cooling units in stationary operation.
The DTI/DTS-cooling units are only approved for stationary operation.
As cooling units of protection category IP 54 the cooling units are largely dust-proof
Limitation: Dust can penetrate despite this under permanent exposure. The cooling units withstand splash water but not a
continuous water jet.
The cooling units are available with different cooling capacities. See the chapter "Refrigeration circuit"for exact performance
data.
The cooling units have a cut-out compatibility with air/air heat exchangers and air/water heat exchangers. The use of aluminum
filters, felt filters or bellows filters is possible with an additional adapter.
The cooling units of the X-series are equipped with the Premium Controller. The control unit can be used to set the operating
parameters. These controllers are control unit for setting refrigeration functions and operating data. They also enable readout of
system messages and diagnostic data.
•
For detailed specifications, see chapters "Technical data", "Electrical connection" and "Operation".
All Pfannenberg cooling units are RoHS compliant and free from:
•
Silicone compounds
•
PCT, asbestos, formaldehyde, cadmium
•
Substances that cause wetting defects
2.1.1
Permissible usage conditions
•
The permissible ambient air temperature of the DTI/DTS cooling units is +15 ... 55 °C (+59 ... 131 °F).
•
The permissible storage temperature of the DTI/DTScooling units is -20 ... +70 °C (-4 ... +158 °F).
•
The operation of the DTI/DTS cooling units is only permissible for stationary assembly and closed switch cabinets.
Operating Manual | Attachment and Installing Cooling Units X-Series | Premium Controller – 230 V | 086100131
8/65