Instruction manual Combi
DO NOT use tools to connect the tubing.
DO NOT operate this product in ambient temperatures below
5 °C (41 °F).
DO NOT operate with incoming water above a temperature of
40 °C (104 °F).
CAUTION: Do not allow any chemicals to come in contact with
this condensate pump. Please remove the pump and water sensor
before using any coil cleaning solutions and other chemicals. Flush
the evaporator coils with water before reinstalling the condensate
pump and water sensor.
Technical data
Maximum flow rate:
Maximum suction:
Maximum head:
Maximum horizontal run:
Sound:
Voltage:
Power:
Alarm relay:
Weight:
Discharge star tube:
Packaging dimensions:
Bulk pack dimensions:
Color:
Protection:
Operation temp:
Compliance:
Cappacity
0
1
2
20
0
1
20
18
18
16
16
14
14
12
12
10
10
8
8
6
6
4
4
2
2
0
0
0
2
4
6
8
10
0
2
4
6
42 l/Hr. (11 GPH)
3 m (9.80 ft.) self priming
20 m (65.60 ft.)
100 m (330 ft.) at 0 head and 0 suction
20dBA at 1 m DIN EN ISO 3741:2011 / DIN EN ISO 3744:2010
100 ~ 240 VAC 50/60 Hz auto sensing universal power input
8W during maximum operation at 110V
7 Amps contacts with integrated replaceable 6.3A fuse 5 × 20 mm
1'000 g (2.2 lb.)
6.25 mm I.D. (1/4") × 1 m (3.3 ft.)
250 x 340 x 54 mm (9.9 x 13.4 x 2.1 inches)
10 Pcs dimensions are 590 x 265 x 365 mm (23.2 x 10.4 x 14.4 inches)
RAL #7040 Grey and RAL #1023 Yellow
Fully potted, IP-44
Ambient 5°C to 40°C (41°F to 104°F) / Water 5°C to 40°C (41°F to 104°F)
Conforms to UL 778, CSA C22.2 #108 and UL 2043 (plenum rated)
Capacity US G/Hr
Capacity US G/Hr
3
4
5
2
3
4
12
14
16
18
20 22
8
10
12
14
16
18
20
Capacity l/Hr
Capacity l/Hr
Ensure the evaporator coils are free of chemicals before reinstalla-
tion of the REFCO Combi pump.
CAUTION: This appliance incorporates an earth connection for
functional purposes only.
Power cable
load.
Alarm cable
completely pressed into the jack.
Only use the original power cable
cable
6
7
8
5
6
7
24 26 28 30 32 34 36 38 40 42 44
22
24
26
28
30
32
Gobi II & Combi at full power
11
must not be entered with a tensile
12
and power cable must be
12
.
9
10
8
9
10
60
50
40
30
20
10
0
34
36
38 40 42
44
Gobi II & Combi at full power
English
11
and alarm
60
50
40
30
20
10
0
3

Publicité

loading

Ce manuel est également adapté pour:

3004146