1. Restart driver board by disconnecting the power connector, wait 10 seconds and reattach
(see D-1 and E-1, Figure 4 on
2. The driver board will go through its normal startup routine.
3. If the faucet IS NOT working properly, first check for error codes by doing the following:
a. Press and hold the TOGGLE button (TB) for 5 seconds.
b. Once you see the "E", keep holding TOGGLE button (TB) for 3 seconds and then press
and release to cycle through and note the error codes:
Driver board will leave Error Code Mode after 10 seconds of inactivity.
NOTICE
1. Redémarrer la carte de commande en déconnectant le connecteur d'alimentation,
attendre 10 secondes et remettre en place (voir D-1 et E-1, figure 4 à la
2. La carte de commande parcourra son cycle de démarrage.
3. Si le robinet ne fonctionne PAS correctement, vérifier d'abord les codes d'erreur en
procédant comme suit :
a. Apuyer et maintenir enfoncé le bouton BASCULEMENT (TB) pendant 5 secondes
b. Une fois que vous voyez le «E», maintenez enfoncé le bouton TOGGLE (TB) pendant 3
secondes, puis appuyez et relâchez pour faire défiler et noter les codes d'erreur :
AVIS
La carte de commande quittera le code erreur mode après 10 secondes d'inactivité.
Error Code
Cause
Code
d'erreur
No sensor/poor
communication with
sensor
Absence de
capteur/mauvaise
communication avec le
capteur
Driver board problem
Problème de carte de
commande
Faucet calibration failure
Défaut d'étalonnage du
robinet
Solenoid fault
Défaut du solénoïde
TROUBLESHOOTING ERROR CODES
CODES D'ERREUR DE DÉPANNAGE
page
6).
1. Confirm sensor is connected and wire harness is not
damaged.
2. Confirm connectors are clean, dry and corrosion
free.
3. If sensor extension cable is used, ensure both ends
are connected.
4. Restart driver board and retest.
1. Restart driver board and retest. If failure continues,
contact Technical Service.
1. Confirm sensor module is connected to the faucet
shank and ensure the faucet and sensor module
are electrically isolated from the sink and any other
conductive materials.
2. Route sensor cables away from power supply wires
of any type.
3. See the "Troubleshooting" on
4. For surface mount box #0, ensure polymer braided
hose is used on both the inlet and outlet of the
solenoid.
1. Confirm solenoid is connected.
Figure 10
page
6).
Solution
page
14.
Page 13 - 23
214189, Rev. C
FS
FC
MB
TB
Solution
1. Confirmer que le capteur est raccordé et le faisceau
de fils n'est pas endommagé.
2. Confirmer que les connecteurs sont propres, secs et
exempts de corrosion.
3. Si le câble d'extension du capteur est utilisé, vous
assurer que les deux extrémités sont reliées.
4. Redémarrer la carte de commande et la tester à
nouveau.
1. Redémarrer la carte de commande et la tester à
nouveau. Si le problème se poursuit, contacter le
service technique.
1. Confirmer que le module de capteur est relié à la
tige de robinet et d'assurer le robinet et le module de
capteur sont isolés électriquement de l'évier et des
autres matériaux conducteurs.
2.
Acheminer les câbles de détecteurs loin des fils
d'alimentation électrique de tout type.
3. Voir la section « Dépannage » à la
4. Pour la boîtier de montage en surface no 0, s'assurer
que tuyau en polymère tressé est utilisé à la fois sur
l'entrée et la sortie du solénoïde.
1. Confirmer que le solénoïde est
page
14.
raccordé.