Base Sounder Indoor,
uninterruptible
1
Installation Notes
Caution!
The products should only be assembled out of direct sunlight,
!
as this is the only way to ensure correct functioning and a long
service life.
Notice!
Installation must only be carried out by authorized specialist
personnel.
If you operate the base sounder without an automatic detector
or a strobe, you must bridge contacts b1 and b2. Only if the
sounders are installed with a detector or strobe, they comply
with EN54-3. Only if the sounder volume is set to the maximum
level, the certified sounds (no. 1, 8, 10, 24) comply with
EN54-3. Certified sound measurements are listed in the
document Bulletin_Sound_Pressure_Level_EN54-3.pdf
(F.01U.263.413), which can be obtained from the manufacturer.
Notice!
Batteries must not be disposed of in household waste. Please
take used batteries to the local collection points. See
www.boschsecurity.com/standards for further information.
2
Technical data
Sound pressure level at a distance of 1 m in dB(A)
Frequency (Hz)
Operating voltage (V DC)
Current consumption in standby (mA)
Current consumption in alarm (mA)
Battery type
Battery capacity (Ah)
Bosch Sicherheitssysteme GmbH
All manuals and user guides at all-guides.com
Installation Notes | en
<93.1
440 to 2900
15 to 33
<1
<3.85
3 V Lithium
2.6
2015.11 | 3.0 | F.01U.216.916