6.
Transport
ATTENTION!
The lifting unit must not be thrown or dropped during transport or installation.
The lifting unit must not be lifted by the power cable!
7.
Electrical connection
/
Observe the correct operating voltage (see "Technical Data").
/
Never place the power plug in water.
/
Connect the lifting unit to a properly installed electrical socket (in compliance with the power
supply company regulations) protected by at least a 10 A (slow-blowing) fuse.
/
For units of protection classification I, all exposed conductive parts are connected with a pro-
tective earth conductor. Before the unit is put into operation, an electrically skilled person must
check that the protective earth cable is properly connected.
/
Temperatures higher than those permitted cause the pump to be shut off by the temperature
limiter. After the temperature limiter is triggered, disconnect the pump from the electric system
before correcting the cause of the fault, otherwise it will switch on automatically once cooled
down.
8.
Set up/installation
ATTENTION!
The relevant standards must be observed.
For use below the backwash level:
/
Guide the discharge line with a loop above the backwash level.
/
If the base of the discharge line loop is more than 5 m above the lifting unit, an additional
checkvalve must be installed.
/
Provide shut off valves.
/
Every drain must be fitted with an odour trap.
Also see installation examples (page 39, figure 3).
33