Applications
Input signals:
Volt -
Potenti-
Current
age
RTD and lin.R
ometer
Connect., wires
4
3
+
+
Output signals:
12
14
13
11
Analogue, 0/4...20 mA and voltage
Supply:
21.6...253 VAC
or
19.2...300 VDC
8
8
All manuals and user guides at all-guides.com
TC
2
44
43
42
41
Relays
24
+
-
23
+
10 V
10 V
-
1 V
1 V
22
21
33
32
31
Order codes:
IAMS0001
Universal transmitter mA out
IAMS0011
Universal transmitter mA / 2 relays
IAMS0010
Universal limit switch with 2 relays
PGMMOD00 Display / programming module
Electrical specifications:
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage, universal ............................ 21.6...253 VAC,
Max. consumption ...................................... ≤ 2.5 W
Fuse ............................................................. 400 mA SB / 250 VAC
Isolation voltage, test / operation ............... 2.3 kVAC / 250 VAC
Communications interface .......................... Programming front PGMMOD00
Signal / noise ratio ...................................... Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%):
Temperature input ................................... ≤ 1 s
mA / V input ............................................ ≤ 400 ms
Calibration temperature .............................. 20...28°C
Accuracy, the greater of the general and basic values:
General values
Input
Absolute
type
accuracy
≤ ±0.1% of span
All
Basic values
Input
type
mA
Volt
Pt100
Lin. R
Potentiometer
TC type: E, J, K, L, N, T, U
TC type: B, R, S, W3, W5, LR
or 19.2...300 VDC
Temperature
coefficient
≤ ±0.01% of span / °C
Basic
Temperature
accuracy
coefficient
≤ ±4 µA
≤ ±0.4 µA / °C
≤ ±20 µV
≤ ±2 µV / °C
≤ ±0.2°C
≤ ±0.01°C / °C
≤ ±0.1 Ω
≤ ±0.01 Ω / °C
≤ ±0.1 Ω
≤ ±0.01 Ω / °C
≤ ±1°C
≤ ±0.05°C / °C
≤ ±2°C
≤ ±0.2°C / °C
9 9