Télécharger Imprimer la page

red lion IAMS 0001 Mode D'emploi page 4

Masquer les pouces Voir aussi pour IAMS 0001:

Publicité

Les langues disponibles

Les langues disponibles

Mounting and connection of the devices should comply with national legislation
for mounting of electric materials, i.a. wire cross section, protective fuse, and
location. Descriptions of input / output and supply connections are shown in the
block diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power
switch, it should be easily accessible and close to the device. The power
switch should be marked with a label indicating that it will switch off the
volt age to the device.
Year of manufacture can be taken from the first two digits in the serial number.
UL INSTALLATION REQUIREMENTS:
Use 60/75°C copper conducters only
For use only in pollution degree 2 or better
Max. ambient temperature ..................... 60°C
Max. wire size ......................................... AWG 26-14
UL file number ........................................ E324843
CALIBRATION AND ADJUSTMENT:
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
NORMAL OPERATION:
Operators are only allowed to adjust and operate devices that are safely fixed
in panels, etc., thus avoiding the danger of personal injury and damage. This
means there is no electrical shock hazard, and the device is easily accessible.
CLEANING:
When disconnected, the devices may be cleaned with a cloth moistened with
distilled water.
LIABILITY:
To the extent that the instructions in this manual are not strictly observed, the
customer cannot advance a demand against Red Lion that would otherwise
exist according to the concluded sales agreement.
4
4
All manuals and user guides at all-guides.com
HOW TO DISMANTLE THE IAMS DEVICES
First, remember to demount the connectors with hazardous voltages.
When front LED lights red / display shows AO.ER:
IAMS0001 and IAMS0011 are designed with a high safety level. Therefore, a
continuous measure ment of the outgoing current is carried out on a 4...20 mA
output signal. If the current is 0, a fatal error mode switches on the red front
LED and disables the relays. If the analogue output is not used, pins 11 and
12 must be short-circuited in order for the device to function. The fatal error
mode can only be reset by switching off and then switching on the supply
voltage to the device.
Picture 1:
Detach the device from the DIN rail
by lifting the bottom lock.
5
5

Publicité

loading

Produits Connexes pour red lion IAMS 0001

Ce manuel est également adapté pour:

Iams 0011Iams 0010